| Plan Review Notes For Permit 16061309 |
| Permit Number |
16061309 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-06 14:25:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ENGINEER IS TO REVIEW THE TAS-105 TEST AND REVISE | | | RAS117 CALCULATIONS (ENGINEERING), FBC 5TH ED. | | | RESIDENTIAL 301. | | | | | | 2. THE PRODUCT APPROVAL PAGES ARE REDUCED AND DIFFICULT | | | TO READ. PLEASE RE-PRINT THE REDUCED PAGES IN LANDSCAPE | | | ORIENTATION, FBC 107. | | | | | | 3. PERMIT 13100612 IS EXPIRED, PLEASE ADDRESS. PROVIDE | | | A COPY OF THE PERMIT CARD, IF AVAILABLE, OR APPLY FOR A | | | "REISSUE" PERMIT AT THE BUILDING DIVISION. | | | | | | 4. RESUB FORM STATES THAT THIS IS FOR "NEW MASTER | | | PLAN." PERMIT APPLICATION 16061309 IS ASSOCIATED WITH A | | | PARCEL AND IS NOT A MASTER PERMIT. IF YOU WOULD LIKE TO | | | APPLY FOR A MASTER PERMIT, SUBMIT A PERMIT APPLICATION | | | AT THE BUILDING DIVISION WITY SEVERAL SETS OF ORIGINAL | | | SIGNED AND SEALED DOCUMENTS. AFTER THAT MASTER PERMIT | | | IS ISSUED, THE PERMITS APPLIED FOR TO DATE CAN BE | | | ISSUED USING THE MASTER. | | | | | | OR, APPLICANT MAY RESUBMIT UNDER EACH APPLICATION. | | | | | | 5. PER K.CONRAD, USE OF THE WITHDRAWAL TEST PERFORMED | | | IN 2015 IS ACCEPTABLE (NO NEW TEST REQUIRED). HOWEVER, | | | PLEASE HAVE THE TEST REPORT REVISED TO INCLUDE THE | | | BRAND OF FASTENER TESTED. | | | |
|