| Plan Review Notes For Permit 16061295 |
| Permit Number |
16061295 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-23 11:21:28 | 1ST REVIEW: FBC 2014 MECHANICAL | | | REVISION #16061295 | | | MASTER #16040429 | | | 6/23/16 | | | | | | 1) I HAVE COPIED AND PASTED BY PROVISO FOR THE MAIN | | | PERMIT APPROVAL BELOW- PLEASE READ. THE SUBMITTED | | | REVISION HAS A NOTE REFERENCING STRUCTURAL DRAWINGS FOR | | | ANCHORING THE CURB TO THE STRUCTURE- PLEASE PROVIDE THE | | | DRAWINGS AND THE WIND LOAD DESIGN CRITERIA FOR THE | | | PROJECT. | | | | | | MECHANICAL PROVISO | | | PERMIT #16040429 | | | 6/3/16 | | | | | | 1) A REVISION IS REQUIRED FOR COMPLETE ENGINEERED TIE | | | DOWN DETAILS FOR ANCHORING THE RTU AND CURB TO THE ROOF | | | STRUCTURE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|