| Plan Review Notes For Permit 16061288 |
| Permit Number |
16061288 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-24 14:46:36 | 1ST REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | GAS COMMENTS; | | | | | | | | | 1. GAS RISER DOES NOT CLEARLY SHOW EXISTING POOL HEATER | | | SHOW LOCATION OF EXISTING POOL HEATER ON RISER. PER WPB | | | AMEND. TO FBC SEC. 107.2.1 | | | | | | 2. CLEARLY INDICATE PRESSURE OF SYSTEM.PER FBC-2014 | | | FUEL GAS SEC. 402.2. | | | | | | 3. THE EXISTING 3/4 FROM METER TI FIRST TEE NEEDS TO BE | | | INCREASED TO 1IN. PER FBC FUEL GAS TABLE TABLE 402.4(1) | | | | | | 4. INDICATE WHAT SIZING TABLES YOU ARE USING. PER WPB | | | AMEND. TO FBC SEC. 107.2.1 |
|