Plan Review Notes
Plan Review Notes For Permit 16061287
Permit Number 16061287
Review Stop E
Sequence Number 1
Notes
Date Text
2016-08-04 14:03:24PER DK ELECTRICAL PLANS ARE A PART OF THE MASTER SET.
2016-07-19 08:40:57ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
 JOB NAME: KFC
 JOB ADDRESS: 4720 BROADWAY
 DESCRIPTION: INSTALL HOOD EXHAUST & SUPPLY PER PLANS
 MAST. PERMIT: 15010897
 REVISION: 16061287
  
  
 1. YOU ARE REFERRING TO THE ABOVE MENTIONED MASTER
 PERMIT FOR APPROVAL AND COMPARISON, BUT THE SUBMITTED
 EXHAUST AND SUPPLY (MAKE UP AIR) IS NOT SIMILAR AS ON
 THE PREVIOUSLY APPROVED DRAWING. THEREFORE AN
 ELECTRICAL PERMIT APPLICATION ACCOMPANIED BY SIGNED AND
 SEALED DRAWINGS REFLECTING THE PROPOSED WORK SHALL BE
 PROVIDED. THE DIAGRAM SHALL INCLUDE MOTOR LOAD CALCS,
 PANEL SCHEDULE AND SINGLE LINE WIRING DIAGRAM INCLUDING
 LIGHTING.
 2. IF THE SYSTEM IS TO BE TIED INTO AN EXISTING FIRE
 ALARM SYSTEM, A SEPARATE FIRE ALARM PERMIT SHALL BE
 SECURED.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  