| 2016-08-04 14:03:24 | PER DK ELECTRICAL PLANS ARE A PART OF THE MASTER SET. |
| 2016-07-19 08:40:57 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | JOB NAME: KFC |
| | JOB ADDRESS: 4720 BROADWAY |
| | DESCRIPTION: INSTALL HOOD EXHAUST & SUPPLY PER PLANS |
| | MAST. PERMIT: 15010897 |
| | REVISION: 16061287 |
| | |
| | |
| | 1. YOU ARE REFERRING TO THE ABOVE MENTIONED MASTER |
| | PERMIT FOR APPROVAL AND COMPARISON, BUT THE SUBMITTED |
| | EXHAUST AND SUPPLY (MAKE UP AIR) IS NOT SIMILAR AS ON |
| | THE PREVIOUSLY APPROVED DRAWING. THEREFORE AN |
| | ELECTRICAL PERMIT APPLICATION ACCOMPANIED BY SIGNED AND |
| | SEALED DRAWINGS REFLECTING THE PROPOSED WORK SHALL BE |
| | PROVIDED. THE DIAGRAM SHALL INCLUDE MOTOR LOAD CALCS, |
| | PANEL SCHEDULE AND SINGLE LINE WIRING DIAGRAM INCLUDING |
| | LIGHTING. |
| | 2. IF THE SYSTEM IS TO BE TIED INTO AN EXISTING FIRE |
| | ALARM SYSTEM, A SEPARATE FIRE ALARM PERMIT SHALL BE |
| | SECURED. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |