| Date |
Text |
| 2017-11-01 18:13:29 | |
| | RESIDENTIAL (R3) REVISION, SIXTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | NOTE: |
| | CONTRACTOR OWES $154.50 FOR PREVIOUS REVISION FEES. NO |
| | MORE REVIEWS WILL BE DONE UNTIL THESE FEES ARE PAID. |
| | FEES FOR CURRENT SUBMITTAL WILL BE ASSESSED ONCE LATEST |
| | SUBMITTAL IS CLARIFIED. |
| | |
| | |
| | 1- NO CLEAR WHAT THE CONTRACTOR IS DOING. CONTRACTOR TO |
| | CLARIFY WHY LATEST DRAWINGS S-2 AND S-3 THAT WERE |
| | SIGNED BY ENGINEER OF RECORD ON 08/10/17 WERE VOIDED. |
| | WHY SUBMITTING OLD DRAWINGS THAT WERE SIGNED AND SEALED |
| | BY THE ENGINEER OF RECORD ON 06/29/16. NO SURE WHAT ARE |
| | THE REVISIONS FOR THIS JOB. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 2- NONE OF THE COMMENTS FROM PREVIOUS CHECKLIST WERE |
| | ADDRESSED. NO CLEAR WHAT THE CONTRACTOR IS DOING. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- I WANT TO REQUEST A MEETING WITH THE CONTRACTOR AND |
| | MY SUPERVISOR TO GET THIS JOB BACK IN TRACK. |
| | |
| | |
| | NOTE: |
| | BELOW IS THE COPY OF PREVIOUS CHECKLIST. NOTHING WAS |
| | ADDRESSED: |
| | |
| | 1- FLAT ROOF FL11946-R7 SUBMITTED: |
| | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL |
| | FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED |
| | BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL |
| | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE |
| | STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON |
| | DETAILS ON SHEET S-3. |
| | SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE |
| | PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS OR DELAYS. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15 |
| | AND NOT INFORMATION WAS PROVIDED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |