| 2017-02-10 10:16:59 | RESIDENTIAL (R3) REVISION, FOURTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- FLAT ROOF FL11946-R7 SUBMITTED: |
| | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WIT THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION |
| | (2014). |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | B) NONE OF THE ASSEMBLIES FROM FLORIDA PRODUCT APPROVAL |
| | FL11946-R7 SUBMITTED MEETS THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES. NEED TO PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR PERIMETER AND CORNER AREAS AS REQUIRED |
| | BY LIMITATION #5.7 OF FLORIDA PRODUCT APPROVAL |
| | SUBMITTED. NEED THE CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.1 FBC-RESIDENTIAL. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 2- CONTRACTOR TO PROVIDE THE ADDITIONAL VALUE TO USE |
| | STEEL BEAMS INSTEAD OF WOOD. INCLUDE THE DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | 3- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | WOOD RAILING BY THE SPECIALTY ENGINEER AS SPECIFIED ON |
| | DETAILS ON SHEET S-3. |
| | SEC. R301.1 FBC 2010. NOTE: THIS INFORMATION NEED TO BE |
| | PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID |
| | CONFLICTS OR DELAYS. |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | NOTE: THIS WAS ALSO REQUESTED ON PROVISO DATED 10/20/15 |
| | AND NOT INFORMATION WAS PROVIDED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |