| 2016-06-24 15:41:02 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ORIGINAL APPROVED PLANS DON'T INCLUDE FLAT ROOF |
| | SYSTEMS. ENGINEER OF RECORD NEEDS TO REVISE PLANS |
| | SPECIFYING THE PROPOSED FLAT ROOF. |
| | PROVIDE TWO SIGNED AND SEALED DRAWINGS SHOWING THE |
| | REVISION. SEC. R301 OF 2010 FBC-RESIDENTIAL. . |
| | |
| | 2- FLAT ROOF NOA 11-0601.10 SUBMITTED IS NOT DESIGNED |
| | FOR FLAT ROOF. THIS NOA IS AN UNDERLAYMENT FOR PITCHED. |
| | ROOFS. REVISE AS REQUIRED. |
| | (A) PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FLAT ROOF |
| | SYSTEM THAT IS DESIGNED FOR THE ROOF DECK FINISH AS |
| | SPECIFIED ON PLANS. |
| | FAC 61G20-3.002(33). |
| | |
| | (B) CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE USED FROM |
| | THE PRODUCT APPROVAL RE-SUBMITTED TO VERIFY COMPLIANCE |
| | WITH THE DESIGN PRESSURES OF SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | (C) IF THE SELECTED ASSEMBLY DOESN'T MEET THE |
| | CALCULATED DESIGN PRESSURES, THEN SIGNED AND SEALED RAS |
| | 117 CALCULATIONS ARE REQUIRED. SEE PRODUCT APPROVAL |
| | SUBMITTED. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | (D) ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) FLAT ROOF PRODUCT APPROVAL AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 3- THIS FLAT ROOF SYSTEM WAS NOT PART OF THE APPROVED |
| | PLANS. SPECIFY THE ADDITIONAL VALUE FOR THE NEW FLAT |
| | ROOF AS REQUIRED BY SEC. 109.3 CITY AMENDMENTS. |
| | |