| 2016-06-24 17:11:39 | 1ST REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | |
| | 1. WATER FOUNTAIN REQUIRED FOR CHANGE OF OCCUPANCY |
| | SHALL COMPLY WITH FBC PL [B] 410.2 MINIMUM NUMBER. |
| | WHERE DRINKING FOUNTAINS ARE REQUIRED, NOT FEWER THAN |
| | TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| | FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS FOR PEOPLE |
| | WHO USE A WHEELCHAIR AND ONE DRINKING FOUNTAIN SHALL |
| | COMPLY WITH THE REQUIREMENTS FOR STANDING PERSONS. |
| | FBC PL TABLE 403.1/ A DRINKING FOUNTAIN COMPILING WITH |
| | FBC ACC 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | 2. A SERVICE SINK IS REQUIRED FOR CHANGE OF OCCUPANCY |
| | SHALL COMPLY WITH FBC PL TABLE 403.1 |
| | |
| | 3. PLEASE PROVIDE WATER RISER DIAGRAM .PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 4. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET SHALL COMPLY WITHE FBC ACC 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 4. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE LAVATORY'S |
| | SHALL COMPLY WITHE FBC ACC 606.2 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 5. PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE WATER |
| | FOUNTAIN SHALL COMPLY WITHE FBC ACC 602.2 CLEAR FLOOR |
| | SPACE. |
| | UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 6. THE DOOR TO BATHROOM SHALL COMPLY WITH FBC ACC |
| | 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | |
| | EXCEPTIONS: |
| | |
| | 1. DOORS TO A TOILET ROOM OR BATHING ROOM FOR A SINGLE |
| | OCCUPANT ACCESSED ONLY THROUGH A PRIVATE OFFICE AND NOT |
| | FOR COMMON USE OR PUBLIC USE SHALL BE PERMITTED TO |
| | SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE PROVIDED |
| | THE SWING OF THE DOOR CAN BE REVERSED TO COMPLY WITH |
| | 603.2.3. |
| | |
| | 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR |
| | INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH |
| | 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE |
| | DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE |
| | CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY |
| | FIXTURE. |
| | |
| | 7. TOILET SHALL COMPLY WITH FBC ACC 604.2 LOCATION. |
| | THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| | TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION, |
| | 604.4 SEATS. |
| | THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| | (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | |
| | 8. GRAB BARS SHALL COMPLY WITH FBC ACC 609.4 POSITION |
| | OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE, |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | DISREGARD COMMENTS BELOW |
| 2016-06-24 09:59:59 | NEED TO CORRECT DRAWING OF VENTING FOR FIXTURES NEED TO |
| | HAVE BETWEEN W/C AND LAV. NEED TO HAVE SIZE OF VENTS ON |
| | DRAWING |