| Plan Review Notes For Permit 16061264 |
| Permit Number |
16061264 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-08 15:09:44 | 1ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CONSERVATION CODES | | | PERMIT 316061264 | | | 7/8/16 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) PROVIDE MECHANICAL PLANS THAT INCLUDE AN AC LAYOUT | | | PLAN, AND A EXHAUST VENTILATION PLAN AND DETAILS FOR | | | THE NEW BATHROOMS- SEE TABLE 403.3. | | | | | | 3) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION | | | AND PROVIDE ENERGY CALCULATIONS FOR THE NEW OCCUPANCY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|