| Plan Review Notes For Permit 16061261 |
| Permit Number |
16061261 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-30 17:03:17 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | - WATER SKIMMER DEVICE MUST COMPLY WITH NEC 680.26(C) | | | POOL WATER BONDING. ( RED LINED ON PLANS ) | | | | | | AN INTENTIONAL BOND OF A MINIMUM CONDUCTIVE SURFACE | | | AREA OF 5800 MM2 (9 IN.2) SHALL BE INSTALLED IN CONTACT | | | WITH THE POOL WATER. | | | THIS BOND SHALL BE PERMITTED TO CONSIST OF PARTS THAT | | | ARE REQUIRED TO BE BONDED IN 680.26(B). |
|