| Plan Review Notes For Permit 16061253 |
| Permit Number |
16061253 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-24 14:18:27 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1) SHEET 1 OF 4 - PER NFPA 72, CONFIRM AND VERIFY 75DB | | | AT THE PILLOW. | | | | | | 18.4.5 SLEEPING AREA REQUIREMENTS. | | | 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO | | | PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A | | | SOUND LEVEL OF AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT | | | SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL | | | HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND | | | LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER, | | | MEASURED AT THE PILLOW LEVEL IN THE AREA REQUIRED TO BE | | | SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA). | | | | | | 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR | | | RETRACTABLE PARTITION, IS LOCATED BETWEEN THE | | | NOTIFICATION APPLIANCE AND THE PILLOW, THE SOUND | | | PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER | | | PLACED BETWEEN THE APPLIANCE AND THE PILLOW. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|