2016-06-24 14:18:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) SHEET 1 OF 4 - PER NFPA 72, CONFIRM AND VERIFY 75DB
 AT THE PILLOW.
  
 18.4.5 SLEEPING AREA REQUIREMENTS.
 18.4.5.1* WHERE AUDIBLE APPLIANCES ARE INSTALLED TO
 PROVIDE SIGNALS FOR SLEEPING AREAS, THEY SHALL HAVE A
 SOUND LEVEL OF AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT
 SOUND LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL
 HAVING A DURATION OF AT LEAST 60 SECONDS OR A SOUND
 LEVEL OF AT LEAST 75 DBA, WHICHEVER IS GREATER,
 MEASURED AT THE PILLOW LEVEL IN THE AREA REQUIRED TO BE
 SERVED BY THE SYSTEM USING THE A-WEIGHTED SCALE (DBA).
  
 18.4.5.2 IF ANY BARRIER, SUCH AS A DOOR, CURTAIN, OR
 RETRACTABLE PARTITION, IS LOCATED BETWEEN THE
 NOTIFICATION APPLIANCE AND THE PILLOW, THE SOUND
 PRESSURE LEVEL SHALL BE MEASURED WITH THE BARRIER
 PLACED BETWEEN THE APPLIANCE AND THE PILLOW.
  
 PETER LEDUC
 FIRE MARSHAL