| Plan Review Notes For Permit 16061232 |
| Permit Number |
16061232 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-23 16:00:35 | 2NDT REVIEW | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | | | | PLUMBING COMMENTS: 2ND REQUEST | | | | | | 1. A GREASE INTERCEPTOR IS REQUIRED FOR 3 COMP SINK AND | | | MOP SINK. PER FBC PL SEC. 1003.3.1 | | | 2. THE 3 COMP SINK SHALL DRAIN INDIRECTLY INTO SANITARY | | | SYSTEM. FBC PL SEC. 802.1.8 FOOD UTENSILS, DISHES, POTS | | | AND PANS SINKS. | | | SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF | | | UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN | | | THE PREPARATION, SERVING OR EATING OF FOOD SHALL | | | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK | | | TO THE DRAINAGE SYSTEM. |
|