2016-06-22 16:10:58REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - INCLUDE TOTAL BUILDING LOAD CALCS AND PANEL SCHEDULES
 ? THE INFORMATION PROVIDED JUST SHOWS THE DEMANDS FOR
 THE NEW 100 AMP SUB PANEL. NEC 215.5
  
 - SPECIFY ON RISER DIAGRAM IF THE 150 MAIN PANEL WILL
 BE FEED THRU LUGS OR AN 100 OCPD WILL BE INSTALLED TO
 PROTECT SUB PANEL ? MINIMUM AIC AND SCR OF ELECTRICAL
 APPARATUS SHALL BE ON PANEL SCHEDULES NEC 110.9 &
 110.10. CLARIFY AND CORRECT ACCORDINGLY.
  
 - PROPER LABELING AND IDENTIFICATION REQUIRED PER NEC
 225.37 & 408.4(A)(B) REFLECT TENANT ADDRESS AND ALL
 CIRCUITS LEGIBABLY MARKED ON ELECTRICAL EQUIPMENT. IN
 ADDITION ARC-FLASH WARNING AND AVAILABLE FAULT CURRENT
 PLAQUES SHALL BE INSTALLED BEFORE FINAL INSPECTION. NEC
 110.16 & 110.24
  
 - NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.