2016-06-23 16:38:56REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - THE ATS EQUIPMENT SHALL BE SERVICE RATED PER NEC
 230.66. HIGHLIGHT ON SPEC SHEET OR MAKE A NOTE ON THE
 RISER DIAGRAM.
  
 - PLEASE SHOW 100 A DISCONNECT INTERGRATED WITH THE
 GENERATOR ON THE RISER DIAGRAM NEC 445.18