| Plan Review Notes For Permit 16061207 |
| Permit Number |
16061207 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-06 06:33:30 | 1) SHT. A11.02 - DETAIL #2 - THE SINK IN THE SOCIAL | | | CENTER SHALL BE LOCATED A MAXIMUM OF 34 INCHES ABOVE | | | THE FINISHED FLOOR PER FBC-ACCESS. SECS.212, 606. | | | 2) WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN | | | FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK, THE | | | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT | | | THAT SHALL CONNECT TO A VENT STACK OR STACK VENT PER | | | 2014 FBC-PLUMBING SEC.918.3.1. INDICATE ON THE PLANS | | | WHAT FLOOR THIS SUITE IS ON AND HOW MANY FLOORS ARE IN | | | THIS BUILDING. | | | 3) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE SINK | | | IN THE SOCIAL CENTER PER 2014 FBC-PLUMBING SEC.607.1. | | | 4) SUBMIT A WATER AND SANITARY RISER PER WPB AMEND. TO | | | FBC. SEC. 107.3.5.1.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|