2016-08-06 06:33:301) SHT. A11.02 - DETAIL #2 - THE SINK IN THE SOCIAL
 CENTER SHALL BE LOCATED A MAXIMUM OF 34 INCHES ABOVE
 THE FINISHED FLOOR PER FBC-ACCESS. SECS.212, 606.
 2) WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN
 FOUR BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT PER
 2014 FBC-PLUMBING SEC.918.3.1. INDICATE ON THE PLANS
 WHAT FLOOR THIS SUITE IS ON AND HOW MANY FLOORS ARE IN
 THIS BUILDING.
 3) HOT OR TEMPERED WATER SHALL BE SUPPLIED TO THE SINK
 IN THE SOCIAL CENTER PER 2014 FBC-PLUMBING SEC.607.1.
 4) SUBMIT A WATER AND SANITARY RISER PER WPB AMEND. TO
 FBC. SEC. 107.3.5.1.3.
  