| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - SITE LIGHTING, FIRE ALARM, ACCESS CONTROL, AND LOW |
| | VOLTAGE (TELEPHONE, DATA, & CAMERAS) SHALL BE SUBMITTED |
| | UNDER A SEPARATE PERMIT WITH SEPARATE SHOP DRAWINGS. |
| | - SHEET E0.03 FOR PROPER CODE REQUIREMENT REFERENCING |
| | THE APPLICABLE WIND LOAD DESIGN IS 170 MPH VERIFY FBC- |
| | 1603.1.4 |
| | - SHEET 3.00 CONFERENCE ROOM AND COLLABORATION TABLES |
| | DATA & POWER OUTLETS, RACEWAY OR ENCLOSURES SHALL BE |
| | SEPARATE UNLESS SAME INSULATION VOLTAGE RATING OF |
| | CONDUCTORS IS USED NEC 300.3(C)(1). BARRIERS MAY BE |
| | INSTALLED IN BOXES IN ACCORDANCE WITH NEC 725 ARTICLES. |
| | - SHEET 3.00 EMPLOYEE SOCIAL CENTER SHALL HAVE GFCI |
| | PROTECTION ON ALL RECEPTACLES WITHIN 6? OF THE |
| | COUNTER-TOP SINK. NEC 210.8(B)(5) MARK ON PLANS. |
| | - GENERAL COMMENT, WORKING CLEARANCE AND ILLUMINATION |
| | IN THE ELECTRICAL ROOM SHALL COMPLY WITH NEC 110.26 AND |
| | CHECKED AT THE TIME OF INSPECTION. LIGHTING MANDATORY |
| | CONTROLS, ENERGY ALLOWANCE LEVELS, AND EMERGENCY |
| | ILLUMINATION ARE IN COMPLIANCE WITH THE FBC, NEC, |
| | FBC-E. |
| | - PANEL SCHEDULE TO INCLUDE AIC AND SCR OF ELECTRICAL |
| | EQUIPMENT NEC 110.10, 110.9. ADD A NOTE IN THE RISER |
| | DIAGRAM FOR ARC-FLASH WARNING LABELS & AVAILABLE FAULT |
| | CURRENT MARKINGS. BOTH IDENTIFICATION PLAQUES SHALL BE |
| | SUITABLE FOR THE ENVIRONMENT INVOLVED NEC 110.16, |
| | 110.24 |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| | CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |