Plan Review Notes
Plan Review Notes For Permit 16061207
Permit Number 16061207
Review Stop E
Sequence Number 1
Notes
Date Text
2016-06-22 18:29:47JOB PERMIT NUMBER: 16061207
 JOB ADDRESS: 501 S FLAGLER DR
 WEST PALM BEACH FLORIDA
 DATE: JUNE 22 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - SITE LIGHTING, FIRE ALARM, ACCESS CONTROL, AND LOW
 VOLTAGE (TELEPHONE, DATA, & CAMERAS) SHALL BE SUBMITTED
 UNDER A SEPARATE PERMIT WITH SEPARATE SHOP DRAWINGS.
 - SHEET E0.03 FOR PROPER CODE REQUIREMENT REFERENCING
 THE APPLICABLE WIND LOAD DESIGN IS 170 MPH VERIFY FBC-
 1603.1.4
 - SHEET 3.00 CONFERENCE ROOM AND COLLABORATION TABLES
 DATA & POWER OUTLETS, RACEWAY OR ENCLOSURES SHALL BE
 SEPARATE UNLESS SAME INSULATION VOLTAGE RATING OF
 CONDUCTORS IS USED NEC 300.3(C)(1). BARRIERS MAY BE
 INSTALLED IN BOXES IN ACCORDANCE WITH NEC 725 ARTICLES.
 - SHEET 3.00 EMPLOYEE SOCIAL CENTER SHALL HAVE GFCI
 PROTECTION ON ALL RECEPTACLES WITHIN 6? OF THE
 COUNTER-TOP SINK. NEC 210.8(B)(5) MARK ON PLANS.
 - GENERAL COMMENT, WORKING CLEARANCE AND ILLUMINATION
 IN THE ELECTRICAL ROOM SHALL COMPLY WITH NEC 110.26 AND
 CHECKED AT THE TIME OF INSPECTION. LIGHTING MANDATORY
 CONTROLS, ENERGY ALLOWANCE LEVELS, AND EMERGENCY
 ILLUMINATION ARE IN COMPLIANCE WITH THE FBC, NEC,
 FBC-E.
 - PANEL SCHEDULE TO INCLUDE AIC AND SCR OF ELECTRICAL
 EQUIPMENT NEC 110.10, 110.9. ADD A NOTE IN THE RISER
 DIAGRAM FOR ARC-FLASH WARNING LABELS & AVAILABLE FAULT
 CURRENT MARKINGS. BOTH IDENTIFICATION PLAQUES SHALL BE
 SUITABLE FOR THE ENVIRONMENT INVOLVED NEC 110.16,
 110.24
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  