2016-08-05 12:35:462ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16061205
 8/5/16
  
 1) COMMENT #9 FROM THE 1ST REVIEW STILL EXISTS- SHEETS
 M0.01, M0.02, HAVE COPIED ELECTRONIC SEALS. ELECTRONIC
 SEALS ARE FOR DIGITAL TRANSFER AND CANNOT BE USED TO
 CERTIFY PAPER PLANS. PLEASE PROVIDE AN ORIGINAL RAISED
 OR INK SEAL AS REQUIRED BY FORIDA STAUTE AND FAC
 61G1-23.002
  
 2) THERE ARE TWO DIFFERENT M0.01 PLAN SHEETS IN THE
 SETS AND THE INDEX NUMBERS ON THE PLANS DO NOT MATCH
 THE NUMBERS IN THE INDEX.- PLEASE CORRECT THESE
 MISTAKES.
  
 3) M2.00: THE SPACES SERVED FOR VAV 11 IN THE SCHEDULE
 ARE NOT CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  