| Plan Review Notes For Permit 16061205 |
| Permit Number |
16061205 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-15 16:29:34 | THIS RESUBMITTED PLAN WAS REVIEWED AND FAILED BY PETER | | | LEDUC, FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET 01.02 - DOOR 100 APPEARS TO BE INSTALLED INTO | | | A FIRE RATED WALL; HOWEVER, THE PLAN AND THE DOOR | | | SCHEDULE DOES NOT INDICATE ANY FIRE RATING. | | | | | | PLEASE CORRECT, VERIFY OR JUSTIFY. | | | | | | 2) SHEET E 0.01 - THERE IS NO INDICATION THAT THE FIRE | | | ALARM WORK SHALL BE SUBMITTED, INSTALLED AND TEST UNDER | | | SEPARATE SHOP DRAWINGS BY A CERTIFIED LIFE SAFETY | | | CONTRACTOR. | | | | | | 3) SHEET 00.30 - DOOR 104 HARDWARE IS INDICATED AS | | | KEYPAD LEVER. THIS DOOR SHALL NO BE LOCKED AGAINST | | | EGRESS AND SHALL COMPLY WITH NFPA 101, CHAPTER 7. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | | | | PLEASE CONFIRMAND PROVIDE AN INDICATING NOTE. | | | | | | 4) SHEET 00.30 - DOOR 100 AND APPLICABLE HARDWARE IS | | | NOT INDICATED ON THE DOOR SCHEDULE. | | | | | | PLEASE CORRECT. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|