2016-07-05 11:51:241ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16061205
 7/5/16
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE ON THE PLAMNS INDICATING THE
 REQUIRED AND PROVIED CFMS OF O/A AIR.
  
 2) SHEETS M0.01 & M2.00: PLEASE PLACE KEY NOTES AT EACH
 VAV BOX LOCATION SHOWN ON THE PLANS TO CLARIFY THE
 SCOPE OF WORK.
  
 3) M2.00: MANY OF THE RETURN REGISTERS SHOWN ON THE
 PLANS DO NOT HAVE LABELS OR CFM QUANTITIES NOTED-
 PLEASE CORRECT.
  
 4) M2.00: INDICATE HOW AIR IS BEING RETURNED FROM THE
 VESTIBULE.
  
 5) M2.00: BRANCH DUCT SIZES FOR VAV 9 NOT SHOWN.
  
 6) M2.00: THE VAV SCHEDULE IS TITLED "EXISTING" HOWEVER
 MANY OF THE BOXES ARE NEW- MPLEASE CORRECT.
  
 7) M2.00: THE SPACES SERVED FOR VAV'S 20 & 21 ARE
 REVERSED IN THE SCHEDULE.
  
 8) M2.00: IDENTIFY THE SPACES BEING SERVED BY VAV'S 8 &
 12 ON THE PLAN.
  
 9) THE MECHANICAL PLAN SHEETS HAVE COPIED ENGINEER'S
 SEALS: ORIGINAL SIGNATURES AND SEALS ARE REQUIRED BY
 FLORIDA STATUTE, AND SECTION 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  