| 2016-07-21 07:38:55 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16061205 |
| | ADD: 501 FLAGLER DR./ ????? SUITE NOR FLOOR LEVEL GIVEN |
| | CONT: TBD |
| | TEL: 904-419-1001 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 21/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE EITHER THE SUITE NUMBER OR FLOOR THE |
| | WORK COVERED UNDER THIS PERMIT WILL OCCUR. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED. |
| | |
| | 2) SHEET A02.01 SHOWS STAIRS 120, WITHIN THE WALL THERE |
| | IS A NOTE # 7 INFILL WALL TO MATCH ADJACENT PARTITION. |
| | THE PLAN DOES NOT INDICATE IF THIS IS A ONE HOUR OR TWO |
| | HOUR RATED VERTICAL EXIT. |
| | 2014 FBC-B 1022.2 CONSTRUCTION. ENCLOSURES FOR INTERIOR |
| | EXIT STAIRWAYS AND RAMPS SHALL BE CONSTRUCTED AS FIRE |
| | BARRIERS IN ACCORDANCE WITH SECTION 707 OR HORIZONTAL |
| | ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711, |
| | OR BOTH. INTERIOR EXIT STAIRWAY AND RAMP ENCLOSURES |
| | SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 |
| | HOURS WHERE CONNECTING FOUR STORIES OR MORE AND NOT |
| | LESS THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR |
| | STORIES. |
| | |
| | 3) SHEET A2.01 STAIR 120 AND THE DOOR INTO THE STAIR. |
| | IT IS UNKNOWN IF THERE IS ANOTHER FLOOR BENEATH THIS |
| | FLOOR WHERE YOU EXIT THE STAIR ENCLOSURE OR IF THIS IS |
| | THE FLOOR OF EXIT DISCHARGE. IF THIS IS THE FLOOR OF |
| | EXIT DISCHARGE FROM THE VERTICAL EXIT THEN THE DOOR |
| | SHOULD BE AN OUTSWING DOOR. 1008.1.2. |
| | |
| | 4) SHEET A2.01 STAIR DOOR 120 DOES NOT SHOW ANY FIRE |
| | RATING SEE DOOR SCHEDULE ON SHEET A00.30. 2014 FBC-B |
| | TABLE 716.5. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |