2016-07-21 07:38:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16061205
 ADD: 501 FLAGLER DR./ ????? SUITE NOR FLOOR LEVEL GIVEN
 CONT: TBD
 TEL: 904-419-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 21/ 2016
 ACTION: DENIED
  
 1) PLEASE PROVIDE EITHER THE SUITE NUMBER OR FLOOR THE
 WORK COVERED UNDER THIS PERMIT WILL OCCUR.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2) SHEET A02.01 SHOWS STAIRS 120, WITHIN THE WALL THERE
 IS A NOTE # 7 INFILL WALL TO MATCH ADJACENT PARTITION.
 THE PLAN DOES NOT INDICATE IF THIS IS A ONE HOUR OR TWO
 HOUR RATED VERTICAL EXIT.
 2014 FBC-B 1022.2 CONSTRUCTION. ENCLOSURES FOR INTERIOR
 EXIT STAIRWAYS AND RAMPS SHALL BE CONSTRUCTED AS FIRE
 BARRIERS IN ACCORDANCE WITH SECTION 707 OR HORIZONTAL
 ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH SECTION 711,
 OR BOTH. INTERIOR EXIT STAIRWAY AND RAMP ENCLOSURES
 SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2
 HOURS WHERE CONNECTING FOUR STORIES OR MORE AND NOT
 LESS THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR
 STORIES.
  
 3) SHEET A2.01 STAIR 120 AND THE DOOR INTO THE STAIR.
 IT IS UNKNOWN IF THERE IS ANOTHER FLOOR BENEATH THIS
 FLOOR WHERE YOU EXIT THE STAIR ENCLOSURE OR IF THIS IS
 THE FLOOR OF EXIT DISCHARGE. IF THIS IS THE FLOOR OF
 EXIT DISCHARGE FROM THE VERTICAL EXIT THEN THE DOOR
 SHOULD BE AN OUTSWING DOOR. 1008.1.2.
  
 4) SHEET A2.01 STAIR DOOR 120 DOES NOT SHOW ANY FIRE
 RATING SEE DOOR SCHEDULE ON SHEET A00.30. 2014 FBC-B
 TABLE 716.5.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved