| Plan Review Notes For Permit 16061203 |
| Permit Number |
16061203 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-08 14:16:14 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE UPDATED CODE REFERENCES AS LISTED | | | ABOVE. | | | 2. GENERAL NOTE TO INDICATED REQUIRED SEPARATE PERMITS | | | FOR LOW VOLTAGE SYSTEMS. | | | 3. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE | | | PER FBC RES E3609.3 | | | 4. CLARIFY WHY GROUNDING ELECTRODE CONDUCTORS IS SHOWN | | | AT PANEL BOARD AND NOT TO COMMON ELECTRODE AT THE METER | | | CAN SERVICE. | | | 5. PROVIDE GENERAL NOTES TO INDICATE REQUIRED AFCI | | | PROTECTION AND TAMPER RESISTANT RECEPTACLES REQUIRED. | | | 6. PROVIDE A NOTE TO INDICATE THAT 75% OF LAMPS ARE TO | | | BE HIGH EFFICACY LAMPS. FBC EC 404.1 | | | 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|