2016-08-08 16:54:14RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- THIS PROPERTY IS LOCATED IN FLOOD ZONE A5. THE
 PROPOSED SCOPE OF WORK IS SUBSTANTIAL IMPROVEMENT. NEED
 TO PROVIDE SURVEY OR ELEVATION CERTIFICATE (2 COPIES)
 SHOWING THE ACTUAL FINISH FLOOR ELEVATION OF THE
 EXISTING HOUSE. IF THE FINISH FLOOR ELEVATION IS LESS
 THAN 7'-6" , THEN THE EXISTING HOUSE AND THE ADDITION
 NEEDS TO HAVE 7'-6" MIN. FINISH FLOOR ELEVATION AS
 REQUIRED BY SEC. 94-546 CITY CODE. PROPERTIES LOCATED
 IN FLOOD ZONES NEED TO COMPLY WITH THE REQUIREMENTS OF
 SEC. R322 FBC-RESIDENTIAL, 5TH EDITION (2014).
 SHOW THE FINISH FLOOR ELEVATIONS FOR THE EXISTING HOUSE
 AND ADDITION ON THE ARCHITECTURAL PLANS.
  
 3- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 FBC-RESIDENTIAL.
  
 4- DRAWING #1 IS REFERENCING THE 2007 FBC. THE CURRENT
 CODE IS THE FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE
 AS REQUIRED. SEC. 553 FLORIDA STATUTE.
  
 5- ACCORDING TO THE SITE PLAN SHOWN ON DRAWING #1, THE
 SETBACK ON THE EAST SIDE IS 5'-0-3/4". THE UNDERSIDE OF
 THE ROOF PROJECTION NEEDS TO COMPLY WITH TABLE
 R302.1(1). PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE FIRE RATING.
  
 6- SPECIFY THE SIZE AND TYPE OF WINDOW IN THE BEDROOM
 LOCATED NEXT TO THE MASTER BATHROOM TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310
 FBC-RESIDENTIAL.. ONE WINDOW WAS ELIMINATED FROM THIS
 BEDROOM TO ALLOW FOR THE ADDITION. SEC. 701.2
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 7- SHEET #3:
 A) FLAT ROOF SLOPE NEEDS TO COMPLY WITH SEC. R905.11.1
 OF FBC-RESIDENTIAL. SLOPE SPECIFIED DOESN'T COMPLY. 5"
 DROP DOESN'T PROVIDE THE REQUIRED SLOPE. REVISE AS
 REQUIRED.
  
 B) PROVIDE COLUMN SCHEDULE FOR ALL CONCRETE BLOCK
 COLUMNS SHOWN ON THE FOUNDATION PLAN. SEC. R601.2
 FBC-RESIDENTIAL.
  
 8- SHEET #4:
 A) REVISE DESIGN DATA NOTE #10:
 (1)THE CURRENT BUILDING CODE IS THE 2014 NOT 2007. SEC.
 553 FLORIDA STATUTE.
 (2)SPECIFY THE ULTIMATE AND NOMINAL WIND LOADS AS
 REQUIRED BY SEC. R301.2.1.3 FBC-RESIDENTIAL.
 (3) THE BUILDING EXPOSURE IS "D" NOT "C". REVISE AS
 REQUIRED BY SEC. R301.2.1.4 FBC-RESIDENTIAL.
  
 B) SPECIFY ALL ROOF DEAD LOADS, LIVE LOADS AND ATTIC
 LIVE LOADS AS REQUIRED BY NOTES "B" AND "G" OF TABLE
 R301.5 FBC-RESIDENTIAL.
  
 C) SECTION 4/4: SEC. R803.2.3.1 REQUIRES 8D RING SHANK
 NAILS. REVISE SPECIFICATIONS FOR THE FLAT ROOF AND
 PITCHED ROOF SHEATHING FASTENING.
  
 9- REVISE THE DOORS AND WINDOWS SHOWN ON DRAWING #2.
 THE DESIGN PRESSURES NEED TO CONFORM TO EXPOSURE "D" AS
 REQUIRED BY SEC. R301.2.1.4 FBC-RESIDENTIAL.
  
 10- SPECIFY SHINGLES ROOF SLOPE TO VERIFY UNDERLAYMENT
 NUMBER OF LAYERS AS REQUIRED BY SEC. R905.2.2
 FBC-RESIDENTIAL.
  
 11- SPECIFY CROSS VENTILATION FOR PITCHED ROOF SHOWING
 COMPLIANCE WITH SEC. R806 FBC-RESIDENTIAL. NOTE: CROSS
 VENTILATION NEEDS TO BE PROVIDED. KEEP IN MIND THAT
 SOFFIT ON THE EAST SIDE CAN NOT HAVE VENTS BECAUSE THE
 UNDERSIDE OF THE PROJECTION NEEDS TO BE FIRE RATED. SEE
 ITEM #5 ABOVE.
  
 12- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE FOAM
 INSULATION SPECIFIED FOR THE FLAT ROOF. DESIGNER OF
 RECORD TO REVIEW AND APPROVE REPORT PRIOR TO SUBMITTAL
 TO THIS OFFICE. SEC. R316 FBC-RESIDENTIAL.
  
 13- ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE LEGIBLE COPIES. LETTERING IS TOO SMALL AND
 CAN NOT BE READ. SEC. 107.2.1.4 CITY AMENDMENTS.
  
 B) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF-FORM
 INCLUDING THE OWNER'S NAME. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED.
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) FLAT ROOF ASSEMBLY SPECIFIED ON PLANS. AND CLEARLY
 IDENTIFY APPROVED ASSEMBLY ON PRODUCT APPROVAL
 SUBMITTED TO VERIFY DESIGN PRESSURES REQUIRED BY SEC.
 R301.2.1 FBC-RESIDENTIAL. . IF THE SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES OF ALL ROOF ZONES,
 THEN SIGNED AND SEALED RAS 117 CALCULATIONS (IF THE
 SELECTED ASSEMBLY ALLOWS IT) WILL BE REQUIRED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND SECTIONS. PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR LIST
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 IMPORTANT: ELEVATION CERTIFICATES WILL BE REQUIRED
 DURING CONSTRUCTION. CONTACT SAMANTHA HILL
 (561)805-6724 OR [email protected] TO AVOID CONFLICTS OR
 DELAYS.
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMITT OLD
 DRAWINGS FOR REFERENCE.
  