| 2016-08-04 10:50:26 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ***NOTE: |
| | THE BUILDING REVIEW MAY BE APPROVED WITH PROVISO. |
| | PROVIDE MEANS THAT ALL THE COMMENTS WILL BE ADDRESSED |
| | AFTER THE PERMIT IS ISSUED AND BEFORE ANY INSPECTIONS |
| | TO AVOID CONFLICTS/DELAYS. FEES MAY APPLY. CONTRACTOR |
| | TO ADVICE IN WRITING IF PROVISO OPTION IS PREFERRED. |
| | |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) CASEMENT WINDOWS AS SPECIFIED ON PLANS. DRAWINGS NO |
| | 1637 SUBMITTED DON'T HAVE A FLORIDA PRODUCT APPROVAL |
| | NUMBER OR MIAMI-DADE NOA NUMBER. PRODUCT NEEDS TO BE |
| | ALREADY APPROVED. IF THERE IS NO APPROVED CURRENT |
| | PRODUCT APPROVAL, THEN MANUFACTURER MAY APPLY FOR LOCAL |
| | PRODUCT APPROVAL. ADVICE IF LOCAL PRODUCT APPROVAL |
| | OPTION IS GOING TO BE CONSIDERED FOR INSTRUCTIONS OF |
| | HOW TO APPLY FOR LOCAL PRODUCT APPROVAL. |
| | |
| | B) FIXED WINDOWS AS SPECIFIED ON PLANS. DRAWINGS NO |
| | 1639 SUBMITTED DON'T HAVE A FLORIDA PRODUCT APPROVAL |
| | NUMBER OR MIAMI-DADE NOA NUMBER. PRODUCT NEEDS TO BE |
| | ALREADY APPROVED. IF THERE IS NO APPROVED CURRENT |
| | PRODUCT APPROVAL, THEN MANUFACTURER MAY APPLY FOR LOCAL |
| | PRODUCT APPROVAL. ADVICE IF LOCAL PRODUCT APPROVAL |
| | OPTION IS GOING TO BE CONSIDERED FOR INSTRUCTIONS OF |
| | HOW TO APPLY FOR LOCAL PRODUCT APPROVAL. |
| | |
| | C) OUTSWING FRENCH DOORS AS SPECIFIED ON PLANS. |
| | DRAWINGS NO 1640A SUBMITTED DON'T HAVE A FLORIDA |
| | PRODUCT APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. |
| | PRODUCT NEEDS TO BE ALREADY APPROVED. IF THERE IS NO |
| | APPROVED CURRENT PRODUCT APPROVAL, THEN MANUFACTURER |
| | MAY APPLY FOR LOCAL PRODUCT APPROVAL. ADVICE IF LOCAL |
| | PRODUCT APPROVAL OPTION IS GOING TO BE CONSIDERED FOR |
| | INSTRUCTIONS OF HOW TO APPLY FOR LOCAL PRODUCT |
| | APPROVAL. |
| | NOTE: CLEARLY IDENTIFY ON PRODUCT APPROVAL SUBMITTED IF |
| | THE SAME TYPE OF DOOR IS GOING TO BE USED FOR ENTRY |
| | DOORS, GREAT ROOM DOORS, LAUNDRY ROOM DOOR AND BALCONY |
| | DOORS. OTHERWISE PROVIDE PRODUCT APPROVAL FOR EACH TYPE |
| | OF DOOR USED FOR EACH LOCATION. |
| | |
| | |
| | D) SLIDING DOORS AS SPECIFIED ON PLANS. NEED DOORS THAT |
| | MEET THE DESIGN PRESSURES SHOWN ON SHEET A3.1. |
| | ALSO, DRAWINGS NO 1650 SUBMITTED DON'T HAVE A FLORIDA |
| | PRODUCT APPROVAL NUMBER OR MIAMI-DADE NOA NUMBER. |
| | PRODUCT NEEDS TO BE ALREADY APPROVED. IF THERE IS NO |
| | APPROVED CURRENT PRODUCT APPROVAL, THEN MANUFACTURER |
| | MAY APPLY FOR LOCAL PRODUCT APPROVAL. ADVICE IF LOCAL |
| | PRODUCT APPROVAL OPTION IS GOING TO BE CONSIDERED FOR |
| | INSTRUCTIONS OF HOW TO APPLY FOR LOCAL PRODUCT |
| | APPROVAL. |
| | |
| | E) WATERPROOFING MATERIAL TO BE USED ON THE BALCONIES. |
| | NOTES: (1) NEED PRODUCT APPROVAL THAT IS LISTED TO |
| | RECEIVE TILES AS SPECIFIED ON PLANS. (2) CLEARLY |
| | IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY UPLIFT DESIGN PRESSURES FOR ALL |
| | BALCONY DECK ZONES. |
| | |
| | F) FLOOD VENTS. SEE COMMENT #3 BELOW. |
| | |
| | 2- STRUCTURAL ENGINEER OF RECORD TO REVIEW AND APPROVE |
| | IN WRITING (NOT SIGNING AND SEALING) ALL THE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 3-THIS PROPERTY IS LOCATED IN FLOOD ZONE A5. THE BASE |
| | FLOOD ELEVATION IS 7'-0". THE FINISH FLOOR ELEVATION |
| | NEEDS TO BE 6" MIN. ABOVE THE BASE FLOOD ELEVATION AS |
| | REQUIRED BY SEC. 94-546 (B)(1) CITY CODE. ACCORDING TO |
| | ELEVATION CERTIFICATE IN CITY RECORDS THE FINISHED |
| | FLOOR ELEVATION OF THE MAIN HOUSE IS 7'-6" AND THE |
| | GARAGE FINISH FLOOR ELEVATION IS 7'-0". THE FINISHED |
| | FLOOR ELEVATION OF THE GARAGE NEEDS TO BE RAISED OR |
| | FLOOD VENTS MAY BE INSTALLED FOR FLOOD CONTROL (SEC. |
| | SEC. 94-546 (A(3) CITY CODE. |
| | NOTE: FLOOD VENTS INSTALLATION OPTION: SHOW LOCATION OF |
| | FLOOD VENTS AND PROVIDE SPECIFICATIONS SHOWING |
| | COMPLIANCE WITH SEC. R322.2.2 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). |
| | |
| | 4- PROVIDE SHOP DRAWINGS FOR ALL NEW RAILINGS AND |
| | BALCONY GUARDRAILS PRIOR TO CONSTRUCTION TO AVOID |
| | CONFLICTS OR DELAYS. NOTE: DESIGNER OF RECORD TO |
| | APPROVE THEM PRIOR TO SUBMITTAL TO THIS OFFICE. SEC. |
| | 107.3.4.2 CITY AMENDMENTS. |
| | |