| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS FOR THE |
| | INSTALLATION OF BRICK VENEER, INCLUDING VENEER SUPPORTS |
| | AT OPENINGS. ALSO, SPECIFY WEEP-HOLES, ETC. |
| | NOTE: PROVIDE COMPLETE DETAILS/ SPECIFICATIONS. DON'T |
| | CITE CODE SECTIONS. |
| | |
| | 2- ENERGY CALCULATIONS WERE REVISED FOR FULL HOUSE |
| | COMPLIANCE INSTEAD OF ADDITION ALONE: |
| | A) REVISE CEILING INSULATION ITEM #10 TO MATCH PLANS. |
| | VENTED AND UNVENTED ROOFS. |
| | B) REVISE ROOF MATERIAL SHOWN ON PAGE 2 OF 5 TO MATCH |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. |
| | C) REVISE CONCRETE BLOCK INSULATION ITEM #9 DOESN'T |
| | MATCH PLANS. SEE DETAIL #2 ON SHEET A-10. |
| | D) REVISE R-VALUE SHOWN ON THE CEILING INSULATION ON |
| | PAGE 3 OF 5 TO MATCH PLANS AND INFORMATION SHOWN ON |
| | ITEM #10. |
| | E) REVISE DOOR TYPE SPECIFIED ON PAGE 3 OF 5 TO MATCH |
| | PLANS AND PRODUCT APPROVALS SUBMITTED. THERE ARE NO |
| | INSULATED DOORS. DOORS WITH GLASS NEED TO BE INCLUDED |
| | IN THE WINDOWS AREA. |
| | F) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| | MATCH PLANS. |
| | G) REVISE NUMBER OF OCCUPANTS ON PAGE 2 OF 5. WHY 20 |
| | PEOPLE IN A SINGLE FAMILY RESIDENCE. |
| | H) REVISE FLOOR TYPES ON PAGE 2 OF 5. 2ND FLOOR IS NOT |
| | ON SLAB ON GRADE. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) GARAGE DOORS THAT MEETS ALL THE DESIGN LOADS SHOWN |
| | ON SHEET S-6 (POSITIVE AND NEGATIVE). |
| | B) DOUBLE EXTERIOR DOORS THAT MEET THE DESIGN PRESSURES |
| | SPECIFIED ON SHEET S-6 FOR FAMILY ROOM AREA. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE |
| | PRODUCT APPROVALS. |