| Notes |
| Date |
Text |
| 2016-08-09 15:39:44 | PLAN DENIED | | | 1) SHOW ACCESS TO NEW A C # 4 AIR HANDLER REFER TO | | | SECTION 403.2.4 AIR HANDLING UNITS 2014 FLORIDA ENERGY | | | CODE. | | | 2) PROVIDE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | | ON THE KITCHEN HOOD.REFER TO SECTION M1503.4 MAKE | | | UP AIR REQUIRED 2014 RESIDENTIAL CODE. | | | 3) REFER TO SECTION M1602.4 BALANCED RETURN AIR | | | EXCEPTION # 3 MASTER SUITE. 2014 FBC RESIDENTIAL | | | CODE. | | | 4) PROVIDE DUCT SIZE ON ALL DUCT SOME NOT LEGIBLE. | | | SECTION 107 FBC | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-85-6676 |
|