| Plan Review Notes For Permit 16061142 |
| Permit Number |
16061142 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-11 11:05:52 | REVISED SHEETS A1.2, A1.3, S1 AND S2 HAVE BEEN | | | APPROVED. | | | | | | REVISED SHEET A4.0 HAS BEEN DENIED FOR THE FOLLOWING | | | REASONS. | | | (1) THE TYPICAL BALCONY DETAIL IS MISSING THE | | | LENGTH/EMBED DEPTH OF THE 5/8" DIAMETER LAG BOLT AND | | | THE 5/8" DIAMETER CONCRETE BOLT. | | | (2) ON THE BALCONY DETAIL, THERE IS A NOTE FOR A 5/8" | | | STRUCTURAL STEEL L-SHAPED WALL ANGLE BRACKET FOR (2) 2 | | | X 8 WD LEDGER SUPPORT WITH FOUR 5/8" DIA. S.S. THRU | | | BOLTS WITH 1-1/2" S.S. WASHERS. THE ARROWS ARE POINTING | | | TO THE INSULATION AND THE L-SHAPED ANGLE BRACKET AND | | | THRU BOLTS ARE NOT SHOWN. PROVIDE DETAILS OF THE L | | | BRACKET WITH THE THICKNESS AND DIMENSIONS. FBC 301.1 | | | (3) THERE IS A SMALL PORTION OF TEXT ON A4.0 BETWEEN | | | DETAIL 2 AND DETAIL 4. IF NOT REQUIRED PLEASE REMOVE. | | | FBC 107.2.1 |
|