| 2016-07-08 18:03:07 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | REVISION BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) REVISED PLAN SHEETS THAT ARE SUBMITTED WITH THE SAME |
| | SHEET NUMBERS AS THE APPROVED PLAN SHEETS ARE INTENDED |
| | TO REPLACE THOSE APPROVED PLAN SHEETS. THEREFORE, ANY |
| | INFORMATION ON THE APPROVED PLANS THAT IS STILL |
| | PERTINENT IS REQUIRED TO BE ON THE NEW SHEETS. THE |
| | REVISED SHEET A-1 IS MISSING THE WINDOW AND DOOR ID |
| | TAGS, AS WELL AS, THE ROOM ID NUMBERS. THE REVISED |
| | SHEET A-6 IS MISSING THE NEW TYPICAL 1-STORY WALL |
| | SECTION, THE SHOWER CURB DETAIL AND THE INTERIOR WALL |
| | DETAIL. FBC 107.2.1 |
| | |
| | 2) ALL OF THE CHANGES ARE REQUIRED TO BE CLOUDED AND |
| | MARKED WITH A TRIANGLE AND THE REVISION NUMBER. THE |
| | REVISIONS SHOULD BE IDENTIFIED IN THE REVISION BOX IN |
| | THE TITLE BLOCK. FBC107.2.1.4 |
| | |
| | 3) ON REVISED SHEET A-6, THE ANCHORS/STRAPS THAT ARE |
| | REQUIRED TO PROVIDE A CONTINUOUS LOAD PATH ARE NOT |
| | SPECIFIED. FBCR 301.1 |
| | |
| | 4) ON REVISED SHEET A-6, THERE ARE NUMEROUS MISTAKES. |
| | THERE ARE ARROWS POINTING TO THE TOP CORD AND THE |
| | BOTTOM CORD OF THE TRUSS FOR THE NOTE THAT SAYS ICYNENE |
| | INSULATION 5/8" GYP. DRYWALL. ONE ARROW HAS A NOTE THAT |
| | SAYS 3/4" PLY EXT. 2" X 6". A BOND BREAK IS REQUIRED |
| | BETWEEN THE STUCCO AND THE WATER-RESISTIVE BARRIER. THE |
| | PLYWOOD WALL SHEATHING IS IDENTIFIED AS 5/8" IN ONE |
| | PLACE AND 3/4" IN ANOTHER. THERE IS NO WASHER SPECIFIED |
| | FOR THE ALL THREAD RODS AT THE BOTTOM PLATES. FBC |
| | 107.2.1 & FBCR 703.6 |
| | |
| | 5) REVISED SHEET S-1 HAS BATHROOM ELEVATIONS AND THE |
| | APPROVED SHEET S-1 HAS FOUNDATION DETAILS WHICH ARE |
| | REQUIRED. THE BATHROOM ELEVATIONS SHOULD HAVE A |
| | DIFFERENT PAGE NUMBER. FBC 107.2.1 |
| | |
| | 6) THE REVISED SHEET S-1 IS NOT SIGNED AND SEALED BY |
| | THE ARCHITECT WHOSE NAME IS LISTED IN THE TITLE BLOCK. |
| | FS 481 |
| | |
| | |
| | |
| | |