| Plan Review Notes For Permit 16061119 |
| Permit Number |
16061119 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-10 12:50:05 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) COMPLY WITH ZONING, 2ND REQUEST | | | | | | 2) PLEASE SHOW A DISCONNECT IN THE ELECTRICAL DIAGRAM | | | AND MARK CIRCUIT AS AN EXISTING 20 AMP DEDICATED | | | CIRCUIT. NEC 600.5 & 600.6, 2ND REQUEST | | | | | | 3) FBC-E SECTIONC405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. ADD A NOTE PLEASE, | | | 2ND REQUEST |
|