| Date |
Text |
| 2016-07-27 15:35:56 | 2ND REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: 2ND REQUEST |
| | |
| | 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION |
| | GUIDE. PER WPB AMEND. TO FBC SEC. 107.2.1 THE |
| | MANUFACTURE SPECIFICATION MUST SHOW COMPLIANCE WITH THE |
| | FSEC STANDARD 101-15 |
| | |
| | |
| | |
| | |
| | 2. PROVIDE PLUMBING RISER DIAGRAM THAT SHOWS COMPLIANCE |
| | WITH FBC M SEC 1402.5.1 PRESSURE AND TEMPERATURE. |
| | SOLAR ENERGY SYSTEM COMPONENTS CONTAINING PRESSURIZED |
| | FLUIDS SHALL BE PROTECTED AGAINST PRESSURES AND |
| | TEMPERATURES EXCEEDING DESIGN LIMITATIONS WITH A |
| | PRESSURE AND TEMPERATURE RELIEF VALVE. EACH SECTION OF |
| | THE SYSTEM IN WHICH EXCESSIVE PRESSURES ARE CAPABLE OF |
| | DEVELOPING SHALL HAVE A RELIEF DEVICE LOCATED SO THAT A |
| | SECTION CANNOT BE VALVED OFF OR OTHERWISE ISOLATED FROM |
| | A RELIEF DEVICE. RELIEF VALVES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF SECTION 1006.4 AND DISCHARGE IN |
| | ACCORDANCE WITH SECTION 1006.6. |
| | 1402.5.3 PROTECTION FROM FREEZING. |
| | SYSTEM COMPONENTS SHALL BE PROTECTED FROM DAMAGE BY |
| | FREEZING OF HEAT TRANSFER LIQUIDS AT THE LOWEST AMBIENT |
| | TEMPERATURES THAT WILL BE ENCOUNTERED DURING THE |
| | OPERATION OF THE SYSTEM. |
| | |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| 2016-07-01 16:43:09 | 1ST REVIEW |
| | |
| | |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION |
| | GUIDE. PER WPB AMEND. TO FBC SEC. 107.2.1 |
| | |
| | 2. PROVIDE PLUMBING RISER DIAGRAM. PER WPB AMEND. TO |
| | FBC SEC. 107.3.5.3(13) |
| | |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |