| Plan Review Notes For Permit 16061069 |
| Permit Number |
16061069 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-20 13:25:57 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PROVIDE THE EXISTING RISER DIAGRAM SHOWING RACEWAY, | | | CONDUCTOR, AND BREAKER SIZES. IN ADDITION SHOW A SITE | | | SPECIFIC FLOOR PLAN INDICATING THE SUB PANEL LOCATION | | | INSIDE THE UNITS. FBC 107 INSUFFICIENT DOCUMENTS. | | | | | | - SMOKE ALARMS ARE REQUIRED PER RESIDENTIAL CODE | | | SECTIONS 314 & 315 INCLUDE LOCATION ON PLANS. | | | | | | - PANEL SCHEDULE SHALL INCLUDE THE AIC RATING OF | | | EQUIPMENT PER NEC 110.9 AND 110.10. |
|