| 2016-06-22 07:25:27 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16061065 |
| | ADD: 2618 BROADWAY UNITS 17-19 |
| | CONT: ALL CLAIMS REPAIRS INC. |
| | TEL: 954-541-0262 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JUNE 22/2016 |
| | ACTION: DENIED |
| | |
| | 1) NEW WALL BETWEEN SLEEPING UNITS IS INDICATED AS A |
| | NON-LOAD BEARING, NON-FIRE RATED WALL. 2014 EXISTING |
| | BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. PLEASE REFER TO THE 2014 |
| | FBC-B: |
| | 2014 FBC-B 420.2 SEPARATION WALLS. WALLS SEPARATING |
| | DWELLING UNITSIN THE SAME BUILDING, WALLS SEPARATING |
| | SLEEPING UNITS IN THE SAME BUILDING AND WALLS |
| | SEPARATING DWELLING OR SLEEPING UNITS FROM OTHER |
| | OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME BUILDING |
| | SHALL BE CONSTRUCTED AS FIRE PARTITIONSIIN ACCORDANCE |
| | WITH SECTION 708. REQUIRING 1 HOUR FIRE SEPARATION. |
| | |
| | SECTION 708 FIRE PARTITIONS. 708.4 CONTINUITY. FIRE |
| | PARTITIONS SHALL EXTEND FROM THE TOP OF THE FOUNDATION |
| | OR FLOOR/CEILING ASSEMBLY BELOW TO THE UNDERSIDE OF THE |
| | FLOOR OR ROOF SHEATHING, SLAB OR DECK ABOVE OR TO THE |
| | FIRE-RESISTANCE-RATED FLOOR/CEILING OR ROOF/CEILING |
| | ASSEMBLY ABOVE, AND SHALL BE SECURELY ATTACHED THERETO. |
| | IN COMBUSTIBLE CONSTRUCTION WHERE THE FIRE PARTITIONS |
| | ARE NOT REQUIRED TO BE CONTINUOUS TO THE SHEATHING, |
| | DECK OR SLAB, THE SPACE BETWEEN THE CEILING AND THE |
| | SHEATHING, DECK OR SLAB ABOVE SHALL BE FIREBLOCKED OR |
| | DRAFTSTOPPED IN ACCORDANCE WITH SECTIONS 718.2 AND |
| | 718.3 AT THE PARTITION LINE. THE SUPPORTING |
| | CONSTRUCTION SHALL BE PROTECTED TO AFFORD THE REQUIRED |
| | FIRE-RESISTANCE RATING OF THE WALL SUPPORTED, EXCEPT |
| | FOR WALLS SEPARATING TENANT SPACES IN COVERED AND OPEN |
| | MALL BUILDINGS, WALLS SEPARATING DWELLING UNITS, WALLS |
| | SEPARATING SLEEPING UNITS AND CORRIDOR WALLS, IN |
| | BUILDINGS OF TYPE IIB, IIIB AND VB CONSTRUCTION. |
| | |
| | 2) IT IS NOT CLEAR IF THE EXTERIOR DOORS ARE BEING |
| | REPLACES SINCE THERE ARE WIND PRESSURES LISTED ON THE |
| | PLANS. IF THE EXTERIOR DOOR IS BEING REPLACED THE |
| | NCOMPLIANCE WITH SECTION FBC-B 1609.6.4.4.1 IS |
| | REQUIRED. 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 |
| | (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS |
| | THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |