2016-09-14 12:34:012ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16061051
 RESTORATION HARDWARE RE-DESIGN
 9/14/16
  
 1) THE REQUESTED AC COOLING AND HEATING CALCULATIONS
 FOR HP-9 & HP-10 WERE NOT SUBMITTED.
  
 2) THE RESUBMITTED ENERGY CALCULATIONS DO NOT PROVIDE
 COMPLIANCE DATA FOR THE NEW HP-9 AND HP-10, AND THE
 ERV.
  
 3) THE COMPLIANCE DATA IN THE RESUBMITTED CALCULATIONS
 DOES NOT MATCH THE DATA IN THE EQUIPMENT SCHEDULES IN
 TERMS OF COOLING AND HEATING CAPACITIES I.E. THE 336
 MBH HP-3 WHICH HAS BEEN GROUPED TOGETHER WITH HP-1 &
 HP-2.
  
 4) SHEET MP100 & FS-210: SHOW THE LOCATION OF THE
 COLDZONE ROOFTOP REFRIGERATION UNIT.
  
 5) THE REQUESTED COMBUSTION, EXHAUST, AND AIR BALANCE
 CALCULATIONS WERE SUBMITTED AS UNSIGNED DOCUMENTS.
 PLEASE PLACE THE CALCULATIONS AND THE AIR BALANCE
 DIAGRAM ON THE PLANS AT THE APPROPRIATE LOCATIONS.
  
 6) M-101, 102, 103, 104: PLEASE PLACE A KEYED NOTE ON
 EACH PLAN SHEET TO CLARIFY THE CONTROL OPERATIONS OF
 THE DUCT SMOKE DETECTORS- SEE SECTION 606.4.
  
 7) M-103 & M-104: PROVIDE AN FD SYMBOL FOR THE DUCTS
 PENETRATING THE FIRE-RATED FLOOR/CEILING ASSEMBLY THE
 LEVEL 4 RESTAURANT AND WINE VAULTS.. THE FD DETAIL ON
 SHEET M301 DOES NOT APPEAR TO BE COMPATIBLE WITH THE
 TYPE OF FLOOR REGISTERS SPECIFIED ON M402. PLEASE NOTE
 ENGINEER APPROVED SUBMITTALS FOR ALL FD'S AND FSD'S ARE
 REQUIRED.
  
 8) M-104: PROVIDE A MEANS OF MAKEUP AIR FOR THE
 CONDENSATE HOOD.
  
 9) PLEASE PROVIDE A REFIGERANT PIPING RISER DRAWING
 WITH PIPE SIZES AND SPECIFICATIONS.
  
 10) AS NOTED IN THE FIRST REVIEW, ALL PROVISOS LISTED
 UNDER THE MASTER PERMIT #15091225 ARE NOW APPLICABLE TO
 THIS REVISION PERMIT, INCLUDING THE REQUIRED REVISIONS
 TO THE REMOVABLE AC PLATFORMS. IT IS HIGHLY RECOMMENDED
 THAT THE DESIGN PROFESSIONALS AND CONTRACTORS PUT
 TOGETHER A SUBMITTAL PACKAGE ADDRESSING ALL PROVISOS AS
 SOON AS POSSIBLE TO AVOID DELAYS DURIONG CONSTRUCTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER