Plan Review Notes
Plan Review Notes For Permit 16061051
Permit Number 16061051
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-20 15:48:561ST REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1. SHT. P-301 PLEASE PROVIDE PLUMBING FIXTURE SCHEDULE.
 PER WPB AMEND.TO FBC SEC. 107.2.1
  
 2. SHT. P-101 IT APPEARS YOU MOVED THE MOP SINK ON THE
 FIRST FLOOR AT GRID LINES A-5.3 AND B5.3 IT IS NOT
 CLEAR ON THE FLOOR PLAN PLEASE CLOUD EVERY CHANGE. PER
 WPB AMEND.TO FBC SEC. 107.2.1
  
 3. SHT. P202.1 THE 2IN. FITTING ON THE VENT FOR TROUGH
 DRAIN IS SHOWN IN THE WRONG FLOW DIRECTION. PER WPB
 AMEND.TO FBC SEC. 107.2.1
  
 4. SHT. P202.1 THE VENT FOR THE MOP SINK ON FIRST FLOOR
 NEEDS TO CONNECT VERTICALLY TO TO HORIZONTAL DRAIN
 SHALL COMPLY WITHE FBC PL SEC. 905.3 VENT CONNECTION TO
 DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
  
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 5.SHT. P 202.1 THE LAV STACK NEXT TO URINAL CAN NOT
 REDUCE IN SIZE FROM 2IN TO 11/2 AND BACK TO 2IN.
  
 6. SHT. P201.1 A NOTE SHOW CONDENSATE DRAIN IN WALL TO
 DISCHARGE INTO FLOOR SINK CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SYSTEM. PER FBC SEC. [M]
 314.2.1 / WPB CODE OF ORD. SEC. 90-126.(5)
  
 7. SHT. P203 THE 2IN VENTS FOR THE FLOOR SINKS ARE
 HORIZONTAL DRY VENTS WHICH ARE NOT ALLOWED THEY SHALL
 COMPLY WITH FBC PL SEC. 905.3-905.4
  
 8. SHT. P201.1/ P301 THESE EQUIPMENT NUMBERS ARE
 MISSING ON THE PLUMBING EQUIPMENT SCHEDULE 3.13, 2.12,
 2.13, 2.14 .PLEASE CLARIFY PER WPB AMEND.TO FBC SEC.
 107.2.1
  
 9. SHT. 201.1 THE EQUIPMENT NUMBERS ARE MISSING 5.02,
 5.03, 5.04, 5.05, 5.06, 5.07, 3.27 PLEASE CLARIFY PER
 WPB AMEND.TO FBC SEC. 107.2.1
  
 10. SHOW FLOW ARROWS ON HOT WATER RECIRCULATION SYSTEM.
 PER WPB AMEND.TO FBC SEC. 107.2.1
  
 11. PROVIDE MANUFACTURE SPEC AND INSTILLATION GUIDES
 FOR TANKLESS HEATERS AND VENTS. PER WPB AMEND.TO FBC
 SEC. 107.2.1
  
 12. PROVIDE DETAIL FOR VENTING ON TANKLESS HEATERS. PER
 WPB AMEND.TO FBC SEC. 107.2.1
  
 13. THE HAND SINKS IN KITCHEN SHALL DISCHARGE INTO
 SANITARY NOT THE GREASE SYSTEM. PER FBC PL
 1003.3.1/1003.2
  
 14. SHT. P206 SHOW SQFT ON STORM RISER DIAGRAM. PER WPB
 AMEND.TO FBC SEC. 107.2.1
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  
  
  
  
  
  