2016-06-27 12:03:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 020 - THE SHEET INDICATES FIRE EXTINQUISHER
 LOCATIONS WITHIN THE STAIRWELLS. AN ALTERNATIVE
 LOCATION SHALL BE INDICATED BASED ON THE FOLLOWING CODE
 REFERENCES
  
 NFPA 101, CHAPTER 36
  
 36.3.5.3 PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED
 IN ALL MERCANTILE OCCUPANCIES IN ACCORDANCE WITH
 9.7.4.1.
  
 NFPA 101, CHAPTER 9
  
 9.7.4 MANUAL EXTINGUISHING EQUIPMENT.
 9.7.4.1* WHERE REQUIRED BY THE PROVISIONS OF ANOTHER
 SECTION OF THIS CODE, PORTABLE FIRE EXTINGUISHERS SHALL
 BE SELECTED, INSTALLED, INSPECTED, AND MAINTAINED IN
 ACCORDANCE WITH NFPA 10, STANDARD FOR PORTABLE FIRE
 EXTINGUISHERS.
  
 NFPA 10
 6.1.3 PLACEMENT.
 6.1.3.1 FIRE EXTINGUISHERS SHALL BE CONSPICUOUSLY
 LOCATED WHERE THEY ARE READILY ACCESSIBLE AND
 IMMEDIATELY AVAILABLE IN THE EVENT OF FIRE.
 6.1.3.2 FIRE EXTINGUISHERS SHALL BE LOCATED ALONG
 NORMAL PATHS OF TRAVEL, INCLUDING EXITS FROM AREAS.
 6.1.3.3 VISUAL OBSTRUCTIONS.
 6.1.3.3.1 FIRE EXTINGUISHERS SHALL NOT BE OBSTRUCTED OR
 OBSCURED FROM VIEW.
  
 ADDITIONALLY:
  
 NFPA 101, CHAPTER 7
  
 7.1.3.2.3* AN EXIT ENCLOSURE SHALL NOT BE USED FOR ANY
 PURPOSE THAT HAS THE POTENTIAL TO INTERFERE WITH ITS
 USE AS AN EXIT AND, IF SO DESIGNATED, AS AN AREA OF
 REFUGE. (SEE ALSO 7.2.2.5.3.)
  
 A.7.1.3.2.3 THIS PROVISION PROHIBITS THE USE OF EXIT
 ENCLOSURES FOR STORAGE OR FOR INSTALLATION OF EQUIPMENT
 NOT NECESSARY FOR SAFETY. OCCUPANCY IS PROHIBITED OTHER
 THAN FOR EGRESS, REFUGE, AND ACCESS. THE INTENT IS THAT
 THE EXIT ENCLOSURE ESSENTIALLY BE ?STERILE? WITH
 RESPECT TO FIRE SAFETY HAZARDS.
  
 THE FIRE EXTINGUISHERS CAN BE LOCATED PRIOR TO THE
 STAIRWAY EXIT DOOR, NOT INSIDE THE STAIRWELL.
  
  
  
 2) SHEET LS 020 - THE INDICATED EXIT CAPACITY ON THE
 FOURTH FLOOR IS 330; HOWEVER, THE EXIT STAIRWAY
 CAPACITY IS 162 EACH, AN EXIT CAPACITY OF 324.
  
 ADDING ALL THE OCCUPANCY LOADS INDICATES A TOTAL 331.
  
 PLEASE CORRECT OR VERIFY.
  
  
  
 3) SHEETS A 003 & FA 160 - THE HOOD SYSTEM IN THE
 KITCHEN AREA SHALL BE PERMITTED UNDER SEPARATE SHOP
 DRAWINGS AND INSTALLED PER NFPA 96.
  
 NFPA 101, CHAPTER 36
 36.3.2.3 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 NFPA 101, CHAPER 9
  
 9.2.3 COMMERCIAL COOKING EQUIPMENT. COMMERCIAL COOKING
 EQUIPMENT SHALL BE IN ACCORDANCE WITH NFPA 96, STANDARD
 FOR VENTILATION CONTROL AND FIRE PROTECTION OF
 COMMERCIAL COOKING OPERATIONS, UNLESS SUCH
 INSTALLATIONS ARE APPROVED EXISTING INSTALLATIONS,
 WHICH SHALL BE PERMITTED TO BE CONTINUED IN SERVICE.
  
 NFPA 96
  
 NFPA 96, CHAPTER 4 GENERAL REQUIREMENTS
 4.1 GENERAL.
 4.1.1 COOKING EQUIPMENT USED IN PROCESSES PRODUCING
 SMOKE OR GREASE-LADEN VAPORS SHALL BE EQUIPPED WITH AN
 EXHAUST SYSTEM THAT COMPLIES WITH ALL THE EQUIPMENT AND
 PERFORMANCE REQUIREMENTS OF THIS STANDARD.
  
 10.1.2* COOKING EQUIPMENT THAT PRODUCES GREASE-LADEN
 VAPORS AND THAT MIGHT BE A SOURCE OF IGNITION OF GREASE
 IN THE HOOD, GREASE REMOVAL DEVICE, OR DUCT SHALL BE
 PROTECTED BY FIRE-EXTINGUISHING EQUIPMENT.
  
 PLEASE PROVIDE A NOTE INDICATING THE ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  