| 2016-07-13 17:58:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. SHEET A020, LEVEL 4, STATES THAT THE EXIT CAPACITY |
| | IS 330 OCCUPANTS, BUT THE STAIR WIDTH (48.75IN) HAS A |
| | CAPACITY OF 162 EACH; REVISE EXIT CAPACITY TO 324 OR |
| | CONTACT ME TO DISCUSS, FBC1003.6, 1005. |
| | |
| | 2. SHEET A020, LEVEL 4, PROPOSED OCCUPANT LOAD OF 359 |
| | OCCUPANTS EXCEEDS THE CAPACITY OF 324, FBC 1003.6. |
| | |
| | 3. SHEET A020, LEVEL 4, OCCUPANT LOADS WERE ROUNDED |
| | DOWN IN TWO CASES, BUT, SINCE IT?S NOT POSSIBLE TO HAVE |
| | A FRACTION OF A PERSON, IT APPEARS THAT ALL OCCUPANT |
| | LOAD CALCS SHOULD ROUND UP, FBC 1004. IT APPEARS THAT |
| | THE TABULAR OCCUPANT LOAD SHOULD BE 361, AND HALF THE |
| | REQUIRED WIDTH WOULD THEN BE 36.1IN FOR DOORS, 54.15 |
| | FOR STAIRS. |
| | |
| | IF USING THE OCCUPANT LOAD ON A020, OCCUPANT LOAD OF |
| | 359 RESULTS IN CAPACITY OF 36.1 AND 35.9, DOOR AND |
| | STAIR, REQUIRED. |
| | |
| | BASED ON THE INFORMATION PROVIDED, THE LOSS OF AN EXIT |
| | WILL RESULT IN LOSS OF OVER HALF THE REQUIRED CAPACITY, |
| | SEE FBC 1005.5. |
| | |
| | IT APPEARS THAT A THIRD EXIT COULD BE APPROPRIATE. |
| | |
| | 4. FBC 5TH EDITION ACCESSIBILITY 604.4, SEE SHEET A120, |
| | TOILET DETAILS DEPICT DIMENSIONS TO THE TOP OF THE LID. |
| | THIS SHOULD BE MEASURED TO THE TOP OF THE SEAT; PLEASE |
| | REVISE. |
| | |
| | 5. FBC 5TH EDITION ACCESSIBILITY 609.4, THE GRAB BAR IS |
| | TO BE MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE |
| | DETAIL DEPICTS THIS AS 36IN MAX, BUT TO THE CENTER OF |
| | THE GRAB BAR; PLEASE REVISE. |
| | |
| | 6. THE SHOWER SEAT IS TO BE WITHIN 3IN OF THE |
| | COMPARTMENT ENTRY, FBC 5TH EDITION ACCESSIBILITY 610. |
| | |
| | 7. PLEASE SEE PLUMBING PLAN REVIEW FOR THE BUILDING |
| | PERMIT 15091225 (THE MASTER FOR THIS REVISION). THE |
| | PLUMBING COMMENTS IN THIS REVIEW ARE REPEAT COMMENTS |
| | FROM A PREVIOUS REVIEW. IT APPEARS THAT THE MASTER |
| | FAILED PLUMBING ACCESSIBILITY, THE PLANS WERE |
| | CORRECTED, PERMIT ISSUED, PLANS REVISED BACK TO THE NON |
| | COMPLIANT DIMENSIONS AND DETAILS FROM THE PREVIOUS |
| | REVIEW. |
| | |
| | PLEASE CONFIRM THAT ALL ACCESSIBILITY ITEMS ARE |
| | COMPLIANT, IN PARTICULAR THE ONES WHICH WERE CHANGED |
| | PREVIOUSLY AND THEN REVISED. IF THEY HAVE BEEN CHANGED |
| | BACK TO ORIGINAL DESIGN BECAUSE YOU DISAGREE WITH THE |
| | COMMENTS, PLEASE CONTACT ME (OR PLUMBING REVIEWER) TO |
| | DISCUSS PRIOR TO RESUBMITTAL. IF THIS IS AN OVERSIGHT, |
| | PLEASE CONFIRM ALL AND REVISE. |
| | |
| | 8. PLEASE ADVISE AS TO WHERE THE DOOR HARDWARE LEGEND |
| | IS LOCATED. SHEET A605 INCLUDES A DOOR SCHEDULE. IF |
| | THIS IS LOCATED IN THE SPEC BOOK, PLEASE INCORPORATE |
| | INTO THE PLAN AS THE SPEC BOOK IS NOT A PART OF THIS |
| | REVIEW. |
| | |
| | 9. ALL GATES WHICH ARE IN THE MEANS OF EGRESS EXIT |
| | DISCHARGE FOR THE ASSEMBLY OCCUPANCY (FOR INSTANCE, SEE |
| | SHEET A107, PEDESTRIAN GATE J3) ARE TO HAVE PANIC |
| | DEVICES OR FIRE EXIT HARDWARE (1008.1.10, ASSEMBLY OVER |
| | 50 AND 1008.2, GATES TO MEET SAME REQUIREMENTS AS |
| | DOORS). REVISE PLAN TO SHOW COMPLIANCE. IT IS SUGGESTED |
| | TO INCLUDE PEDESTRIAN GATES IN OR NEAR THE DOOR |
| | SCHEDULE. |
| | |
| | 10. AS I WAS NOT ABLE TO LOCATE THE HARDWARE SCHEDULE, |
| | PLEASE CONFIRM THAT ALL DOORS IN THE MEANS OF EGRESS |
| | FOR THE 4TH FLOOR, ASSEMBLY OCCUPANCY INCLUDE PANIC |
| | DEVICES OR FIRE EXIT HARDWARE AND REVISE PLAN TO SHOW |
| | COMPLIANCE, FBC 5TH EDITION 1008.1.10 (OR ADVISE AS TO |
| | THE LOCATION OF THE HARDWARE SCHEDULE); REVISE AS |
| | NECESSARY. |
| | |
| | 11. A003, BUILDING DATA, REVISE TO INCLUDE THE NEW |
| | OCCUPANCY. AS THIS IS A NON SEPARATED MIXED OCCUPANCY |
| | BUILDING, THE BUILDING HEIGHT AND DATA SHOULD UTILIZE |
| | THE NUMBERS FOR A2. TO DOCUMENT COMPLIANCE WITH FBC |
| | TABLE 503, PLEASE ALSO INCLUDE THE SF AREA ALLOWED, |
| | PLUS SPRINKLER INCREASE, TO CLEARLY DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 12. A751 AND ANY OTHER LOCATIONS AS APPLICABLE, REVISE |
| | POS DETAIL TO SHOW COMPLIANCE WITH FBC 5TH EDITION |
| | ACCESSIBILITY 904, SALES AND SERVICE COUNTERS. |
| | |
| | 13. DESIGN SERVICES DESK AND COUNTER (SUCH AS ON SHEET |
| | A102 BUT MAY ALSO BE IN OTHER LOCATIONS), EITHER |
| | PROVIDE A DETAIL SHOWING COMPLIANCE WITH ACCESSIBILITY |
| | OR THIS REVISION WILL BE ISSUED WITH PROVISO TO PROVIDE |
| | PRIOR TO INSTALLATION. |
| | |
| | 14. REGARDING WM. SMITH, PE AND JACOB HEMKE, PE, PLEASE |
| | PROVIDE EVIDENCE OF THE ADVANCED FBC COURSE (UNLESS THE |
| | WEBSITE MYFLORIDALICENSE.COM HAS BEEN UPDATED TO |
| | REFLECT THAT THESE TWO ENGINEERS HAVE TAKEN THE |
| | COURSE). |
| | |
| | ALL ENGINEERS ARE REQUIRED TO TAKE A FLORIDA BUILDING |
| | CODE COURSE BY JUNE 30, 2016 (PER FS 471.0195, |
| | FAC61G15-22.001). FLORIDA STATUTE 471.0195 REQUIRES |
| | THAT ENGINEERS WHO HAVE NOT TAKEN THE COURSE BY THIS |
| | DATE BE REPORTED TO FBPE. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |