| Plan Review Notes For Permit 16061017 |
| Permit Number |
16061017 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-08 08:47:14 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA RES BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE UPDATE ALL CODE REFERENCES TO REFLECT ABOVE | | | STATED STANDARDS. | | | 2. LABEL NEW RECEPTACLE AT GARAGE TO GFCI PROTECTED | | | E3902.6 | | | 3. SHOW AND PROVIDE A COMPLETE ELECTRICAL LOAD | | | CALCULATION REFLECTING ALL NEW LOADS. FBC 107.3.5 | | | 4. THE STRUCTURE SHOWN IS A DETACHED GARAGE WHICH WILL | | | REQUIRE A PANELBOARDS AT THE GARAGE LOCATION PER NEC | | | 225.30. | | | 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | | QUESTIONS REGARDING THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|