| 2016-08-03 10:47:51 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC. |
| | THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE |
| | 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT |
| | DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC |
| | FIFTH EDITION. |
| | |
| | 2) THE 2014 FBC REFERENCES ASCE 7-10 AND 2010 NFPA-72. |
| | PLEASE UPDATE. |
| | |
| | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| | APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE 8' X |
| | 7' OVER HEAD SECTIONAL GARAGE DOORS AND THE 3' X 7' |
| | OUTSWING DOOR. |
| | |
| | 4) THE NOA THAT FOR THE GAF ROOL ROOFING (NOA |
| | NO.15-0707.10) IS MISSING PAGES, IS FOR USE AS AN |
| | UNDERLAYMENT AND IS DESIGNED FOR ROOFS HAVING A MINIMUM |
| | SLOPE OF 2:12. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR |
| | A ROOF COVERING FOR ROOFS WITH A 1/4" PER FOOT SLOPE |
| | THAT HAS DESIGN PRESSURES THAT MEET THE UPLIFT |
| | REQUIREMENTS FOR EXPOSURE C WITH A 170 MPH VULT |
| | WINDSPEED. SUBMIT SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING FOR PERIMETER AND |
| | CORNER ROOF AREAS IF REQUIRED. FBC R301.2.1 |
| | |
| | 5) SPECIFY THE SLOPE OF THE GARAGE ROOF ON THE PLANS. |
| | FBC 107.2.1 |
| | |
| | 6) SHOW COMPLIANCE WITH FBC R309.1 THE AREA OF FLOOR |
| | USED FOR PARKING OF AUTOMOBILES OR OTHER VEHICLES SHALL |
| | BE SLOPED TO FACILITATE THE MOVEMENT OF LIQUIDS TO A |
| | DRAIN OR TOWARD THE MAIN VEHICLE ENTRY DOORWAY. |
| | |
| | |
| | |
| | |
| | |
| | |