2016-06-21 12:31:53NFPA 90A-6.4, 2012 EDITION: SMOKE DETECTION FOR
 AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2 LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY. OR 5 TON UNITS.
  
 NFPA 90A-6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY
 SECTION 6.4 ARE INSTALLED IN A BUILDING NOT EQUIPPED
 WITH AN APPROVED FIRE
 ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE FOLLOWING
 SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
 6.4.4.4 SMOKE DETECTORS POWERED SEPARATELY FROM THE
 FIRE ALARM SYSTEM FOR THE SOLE FUNCTION OF STOPPING
 FANS SHALL NOT REQUIRE STANDBY POWER.
  
  