Plan Review Notes
Plan Review Notes For Permit 16060976
Permit Number 16060976
Review Stop B
Sequence Number 1
Notes
Date Text
2016-06-17 07:27:37BUILDING PLAN REVIEW
 W. P. B. REVISION: 16060976
 W. P. B. PERMIT: 16050638
 ADD: 901 45TH ST. ST. MARY'S MEDICAL CENTER
 CONT: WESTBROOKE
 TEL: 561-395-4126
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 17/2016
 ACTION: DENIED
  
 1) SHEET A0.2 THE PLEASE REVIEW THE SIGNAGE HEIGHT THAT
 SHOW THE BRILLE INSERTS. THE PLAN SHOWS THE SIGNS
 CENTERED ON THE 60 INCHES, PLEASE NOTE ON THE PLANS
 THERE IS A SECOND REQUIREMENT THAT ALSO NEEDS TO BE
 MET. THAT IS THE BRAILLE PORTION OF THE SIGN MUST BE 48
 INCHES TO THE HIGHEST PORTION OF THE BRAILLE TO BE IN
 COMPLIANCE WITH REACH RANGES.
 2014 FBC-ACCESS. CODE 703.4.1 HEIGHT ABOVE FINISH FLOOR
 OR GROUND. TACTILE CHARACTERS ON SIGNS SHALL BE LOCATED
 48 INCHES (1220 MM) MINIMUM ABOVE THE FINISH FLOOR OR
 GROUND SURFACE, MEASURED FROM THE BASELINE OF THE
 LOWEST TACTILE CHARACTER AND 60 INCHES (1525 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND SURFACE,
 MEASURED FROM THE BASELINE OF THE HIGHEST TACTILE
 CHARACTER.
 2014 FBC-ACCESS. CODE 308.2 FORWARD REACH
 2014 FBC-ACCESS. CODE 308.3 SIDE REACH
  
 2) SHEET A7.2 THE DOOR SCHEDULE DOOR # 2 BEING A
 2'-10", THE ACCESS. THE ACCESS. CODE ALLOWS IN
 ALTERATIONS A PROJECTION OF 5/8 INCH (16 MM) MAXIMUM
 INTO THE REQUIRED CLEAR WIDTH SHALL BE PERMITTED FOR
 THE LATCH SIDE STOP.
 THE 2014 EXISTING BUILD. CODE DOES NOT ADDRESS THIS
 ISSUE. THE 2014 FBC-B SECTION 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  