| 2016-06-17 05:09:38 | 1) SUBMIT TWO COPIES OF THE TANKLESS WATER HEATER |
| | SPECS.WPB AMEND. TO FBC SEC. 107.1. |
| | 2) IS THIS TANKLESS WATER HEATER REPLACING AN EXISTING |
| | TANKLESS WATER HEATER OR IS IT REPLACING A STORAGE TANK |
| | TYPE WATER HEATER OR IS IT BEING ADDED TO THEEXISTING |
| | HOT WATER SYSTEM? INDICATE ON THE APPLICATION IN THE |
| | DESCRIPTION OF WORK. |
| | 3) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE NEW |
| | TANKLESS WATER HEATER. |
| | 4) IS THIS TANKLESS WATER BEING ADDED TO AN EXISTING |
| | GAS SYSTEM? SUBMIT A COMPLETE GAS RISER WITH ALL PIPE |
| | SIZES, TYPE OF PIPE, THE DEVELOPED LENGTH TO THE |
| | FURTHEST GAS OUTLET, THE BTU LOAD OF EACH APPLIANCE, |
| | THE PSI OF THE SYSTEM, TYPE OF GAS AND THE TOTAL BTU |
| | LOAD ON THE SYSTEM.DO THE SAME IF IT IS A NEW GAS |
| | SYSTEM |
| | 5) TYPE OF GAS (LP OR NATURAL). |
| | 6) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | 7) AN ADDITIONAL APPLICATION IS REQUIRED TO INSTALL THE |
| | WATER LINES FOR THE HEATER. |
| | |