| 2016-06-16 18:49:58 | RESIDENTIAL (R3) ENTRY DOOR REPLACEMENT, BUILDING | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION(2014) | | | | | | 1- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, 5TH | | | EDITION (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" | | | NOT EXPOSURE "B" AS SHOWN ON WIND-LOADS TABLE | | | SUBMITTED. THE DOOR PRODUCT APPROVAL FL17184-R3 | | | SUBMITTED DOESN'T MEET THE DESIGN PRESSURES SHOWN ON | | | THE WIND- LOAD TABLE SUBMITTED. PROVIDE PRODUCT | | | APPROVAL THAT MEETS THE CALCULATED DESIGN PRESSURES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|