2016-06-20 11:30:521ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16060843
 6/20/16
  
 1) CLARIFY HOW THE COOLING AND HEATING FOR THE PROPOSED
 NEW OCCUPANCY WAS SIZED- PROVIDE CALCULATIONS.
  
 2) SPACE HEATING IS REQUIRED FOR ALL OCCUPIED ROOMS AND
 SPACES PER SECTION 309.1, HOWEVER VAV'S #2 & 3 ARE NOT
 EQUIPPED WITH HEAT- PLEASE CLARIFY.
  
 3) THE 12X10 TRANSFER DUCT FROM OFFICE 904 IS
 UNDERSIZED- SECTION 601.5.
  
 4) PLEASE INDICATE THE RETURN AIR CFM'S AT THE THE
 60X16 TRANSFER- IT APPEARS TO BE UNDERSIZED PER SECTION
 601.5.
  
 5) THE ENGINEER OF RECORD MUST PLACE HIS SIGNATURE AND
 SEAL ON THE MECHANICAL PLAN SHEETS- SECTION
 61G15-23.002 FORIDA ADMINISTRATIVE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER