| Plan Review Notes For Permit 16060843 |
| Permit Number |
16060843 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-20 11:30:52 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16060843 | | | 6/20/16 | | | | | | 1) CLARIFY HOW THE COOLING AND HEATING FOR THE PROPOSED | | | NEW OCCUPANCY WAS SIZED- PROVIDE CALCULATIONS. | | | | | | 2) SPACE HEATING IS REQUIRED FOR ALL OCCUPIED ROOMS AND | | | SPACES PER SECTION 309.1, HOWEVER VAV'S #2 & 3 ARE NOT | | | EQUIPPED WITH HEAT- PLEASE CLARIFY. | | | | | | 3) THE 12X10 TRANSFER DUCT FROM OFFICE 904 IS | | | UNDERSIZED- SECTION 601.5. | | | | | | 4) PLEASE INDICATE THE RETURN AIR CFM'S AT THE THE | | | 60X16 TRANSFER- IT APPEARS TO BE UNDERSIZED PER SECTION | | | 601.5. | | | | | | 5) THE ENGINEER OF RECORD MUST PLACE HIS SIGNATURE AND | | | SEAL ON THE MECHANICAL PLAN SHEETS- SECTION | | | 61G15-23.002 FORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|