Plan Review Notes
Plan Review Notes For Permit 16060843
Permit Number 16060843
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-06-21 16:33:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1.1.1 - THE OFFICE ENTRY WALL IS INDICATED
 AS A WALL TO EXTEND TO ABOVE CEILING. SHEET AD 1.1
 INDICATES THE REMOVAL OF A 1 HOUR WALL SECTION TO
 ACCOMODATE THIS ENTRY WAY. A 1 HOUR RATED WALL AND DOOR
 SHALL BE INSTALLED AT THIS LOCATION.
  
 PLEASE PROVIDE REVISED DETAILS FOR A 1 HOUR WALL OR
 CLARIFY.
  
 2) SHEET A 1.1.1 - DOOR 901 IS NOT INDICATED AS A FIRE
 RATED DOOR. PER THE ABOVE NOTED WALL REVISION, DOOR 901
 IS REQUIRED TO BE RATED.
  
 PLEASE CORRECT OR CLARIFY.
  
 3) PLEASE SEE BUILDING COMMENTS REGARDING PLAN SIGNED
 AND SEALED REQUIREMENTS.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL