| Plan Review Notes For Permit 16060843 |
| Permit Number |
16060843 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-06-27 11:37:00 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. GENERAL NOTES- PROVIDE A BLOCK NOTE INDICATING THE | | | REQUIRED SEPARATE PERMITS AND DATA CUT SHEET SUBMITTALS | | | FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED | | | TO PHONE AND DATA, ETC. A NOTE WILL SUFFICE. | | | 2. PROVIDE A NOTE TO COMPLY WITH FBC ENERGY | | | CONSERVATION 2014- 50% OF RECEPTACLES TO BE | | | AUTOMATICALLY CONTROLLED. FBC EC C407.7 | | | 3. EOR TO SIGN AND SEAL DRAWINGS SUBMITTED. | | | 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | | THIS PROJECT. | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | |
|