| Notes |
| Date |
Text |
| 2016-06-21 14:27:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) SHEET A 1.1 - THE REMODEL CREATES A SIGNIFICANT | | | CHANGE IN THE ELEVATOR LOBBY AREA. THERE IS NO | | | INDICATION OF APPROVAL FROM THE ENGINEER OF RECORD OR | | | OTHER QUALIFIED ENTITY REGARDING THE ELEVATOR LOBBY | | | PROTECTION, ELEVATOR SHAFT PRESSURIZATION, SMOKE EVAC, | | | SMOKE CONTROL OF THE EXISTING SYSTEMS AND THEIR EFFECT | | | ON THE PROPOSED INSTALLATION. | | | | | | PLEASE PROVIDE A QUALIFIED AND COMPLIANT REVIEW OF THE | | | EXISTING LIFE SAFETY SYSTEMS FEATURES OF THE ELEVATORS | | | AND LOBBY AREA IN RELATION TO THE PROPOSED. | | | | | | 2) SHEET A 1.1 - THE NEWLY CREATED ELEVATOR LOBBY | | | CORRIDORS DO NOT INDICATE RATED OR SMOKE PARTITION | | | WALLS. PLEASE PROVIDE A REVIEW INDICATING THE | | | APPROPRIATE LIFE SAFETY FEATURE FOR THESE NEW WALLS. | | | | | | 3) SHEET A 1.1 - DOOR # 4 IS INDICATED AND IS | | | IN-SWINGING. IS THIS DOOR FUNCTIONING AS A REQUIRED | | | EXIT? | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN OF THE ENTIRE SPACE | | | AS THE EXISTING EXITS HAVE BEEN MODIFIED AND TO ENSURE | | | PROPER OCCUPANCY LOAD EXIT REQUIREMENTS ARE MET PER | | | NFPA 101, CHAPTER 7. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|