| 2016-07-19 14:18:27 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: NEW COMMON CORRIDOR FOR 17TH FLOOR |
| | JOB ADDRESS: 525 OKEECHOBEE BLVD. |
| | DESCRIPTION: COMMERCIAL DEMO AND SUBSEQUENT ALTERATION |
| | ON TWO SEPARATE PERMITS. |
| | MAST. PERMIT: 16060841/16060841 |
| | REVISION: N/A |
| | |
| | IN ADDITION TO THE PREVIOUS FIRE AND ELECTRICAL |
| | COMMENTS, PLEASE NOTE THE FOLLOWING: |
| | 1. FBC-E405.7 REQUIRES AUTOMATIC RECEPTACLE CONTROL |
| | 2. FBC.B1011 HAS SPECIFIC EXIT LIGHT REQUIREMENTS WHICH |
| | HAVE NOT BEEN MET. |
| | 3. NEC 422.52 REQUIRES GFCI PROTECTION FOR DRINKING |
| | FOUNTAIN CIRCUITS. THE COVER SHEET INDICATES THAT A NEW |
| | ADA COMPLIANT WATER FOUNTAIN IS BEING INSTALLED, YET |
| | THERE IS NO MENTION OF THIS IN THE ELECTRICAL SHEETS OR |
| | THE ELECTRICAL PANEL SCHEDULES. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |
| | |
| | |
| 2016-06-27 12:12:05 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 NEC |
| | COMMENTS: |
| | |
| | 1. ADDRESS FIRE COMMENT FOR AN ELECTRICAL APPROVAL. |
| | 2. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. FEEL |
| | FREE TO CONTACT ME AT THE NUMBER BELOW SHOULD YOU HAVE |
| | ANY QUESTIONS OR CONCERN. |
| | |
| | |
| | |
| | VALENTINO PEREZ |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6717 |
| | [email protected] |
| | |