16060834 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-02 07:34:39 | M1602.4 BALANCED RETURN AIR. EXCEPTIONS: 1. TRANSFER | | | DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN | | | TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA (SQUARE | | | INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR SPACE | | | IT IS SERVING AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER | | | RETURN AIR BALANCE. THE 10 INCH DIAMETER TRANSFER DUCT | | | IS TOO SMALL FOR A 9 INCH DIAMETER SUPPLY. | | | |
|