2016-08-02 07:34:39M1602.4 BALANCED RETURN AIR. EXCEPTIONS: 1. TRANSFER
 DUCTS MAY ACHIEVE THIS BY INCREASING THE RETURN
 TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA (SQUARE
 INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR SPACE
 IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH (25 MM) UNDERCUT TO ACHIEVE PROPER
 RETURN AIR BALANCE. THE 10 INCH DIAMETER TRANSFER DUCT
 IS TOO SMALL FOR A 9 INCH DIAMETER SUPPLY.
  