Plan Review Notes
Plan Review Notes For Permit 16060834
Permit Number 16060834
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-07 12:55:05REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL.
 NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. OR
 MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. ( SEEMS TO BE
 MISSING A RECEPTACLE BY THE DOOR. )
  
 - NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 ( ADD A NOTE )
  
 - PLEASE MODIFY THE EXTERIOR GFCI OUTLET TO HAVE SLASH
 RATING "WR/WP" .NEC 406.9(B) RECEPTACLES IN WET
 LOCATIONS.