| 2017-01-12 15:50:48 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | ***REGARDING COMMENTS RELATED TO TITLE BLOCK ISSUES: DO |
| | NOT REVISE SHEET AT THIS TIME UNLESS THE SHEET IS |
| | REVISED TO ADDRESS OTHER COMMENTS*** |
| | |
| | 1. SHEET A.009, ADA DETAILS INCLUDE DIMENSIONS WHICH DO |
| | NOT COMPLY, OR COMPLIANCE NOT CLEAR. FOR INSTANCE, FBC |
| | A 604.4 REQUIRES THAT THE TOP OF THE SEAT BE 17" - 19", |
| | DETAILS ARE NOT CLEAR IF THEY MEASURE TO THE TOP OF THE |
| | SEAT OR THE TOP OF THE LID. 609.4 REQUIRES THAT THE |
| | GRAB BARS BE MEASURED TO THE TOP OF THE BAR; DETAILS |
| | MEASURE TO THE CENTER OF THE BAR. AS THIS IS A |
| | FOUNDATION PERMIT, ALL DETAILS WERE NOT REVIEWED. |
| | REVISE OR REMOVE DETAILS. |
| | |
| | IF NOT NEEDED BY OTHERS, IT IS ACCEPTABLE TO REMOVE |
| | THESE PAGES. |
| | |
| | 2. SHERRI K. GUTIERREZ (AR92855) SIGNED AND SEALED SOME |
| | SHEETS, ANNE SETON COTTER (ILLEGIBLE LICENSE NUMBER) |
| | SEALED OTHER SHEETS. PLEASE ALSO SEE FS481, THE |
| | ARCHITECT'S TITLE BLOCK IS TO INCLUDE THE PRINTED NAME |
| | AND LICENSE NUMBER OF THE INDIVIDUAL SIGNING AND |
| | SEALING THE SHEET, AND THE CERTIFICATE OF AUTHORIZATION |
| | FOR THE FIRM. |
| | |
| | IS IT DESIGNER'S INTENT TO HAVE TWO ARCHITECTS FOR THIS |
| | PROJECT? IF PORTIONS WILL BE DESIGNED BY SOMEONE OTHER |
| | THAN THE ARCHITECT OF RECORD, PLEASE CONTACT ME. IF |
| | NOT, PROVIDE ALL PLAN SHEETS WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED PREPARED BY THE ARCHITECT OF RECORD. |
| | (I DO NOT CONSIDER RENDERINGS SHEETS REQUIRED TO BE |
| | SIGNED AND SEALED) |
| | |
| | THE COVER SHEET STATES THAT ARCHITECT OF RECORD IS |
| | SHERRI K. GUTIERREZ AND THAT SHEET INCLUDES THE |
| | THRESHOLD STATEMENT. |
| | |
| | 3. SHEET A.010 INCLUDES OUTDATED CODE STANDARDS |
| | THROUGHOUT THE PAGE; FOR INSTANCE, ADA CONDO GENERAL |
| | NOTES 1 STATES "TO COMPLY WITH THE 2007 FLORIDA |
| | BUILDING CODE". CHECK ALL REFERENCES AND REVISE. |
| | |
| | 4. CIVIL SHEETS DO NOT STATE WHETHER VERTICAL DATUM IS |
| | NGVD29 OR NAVD88. THIS IS INCLUDED ON THE COVER SHEET |
| | BUT IT IS RECOMMENDED THAT THIS INFORMATION BE |
| | INCORPORATED INTO ALL SHEETS. |
| | |
| | 5. ALL ENGINEERS WHO DESIGN UNDER FBC ARE TO TAKE AN |
| | ADVANCED FLORIDA BUILDING CODE COURSE WITHIN ONE YEAR |
| | OF ADOPTION. THIS COURSE WAS DUE BY JUNE 30, 2016. THE |
| | WEBSITE MYFLORIDABUILDING.ORG DOES NOT REFLECT THAT ALL |
| | OF THE ENGINEERS HAVE TAKEN THIS COURSE. PLEASE CONTACT |
| | FBPE IF THE WEBSITE IS INCORRECT. IF CORRECT, PLEASE |
| | RESOLVE. THIS WILL NOT PREVENT PERMIT ISSUANCE BUT THE |
| | BUILDING DEPARTMENT IS REQUIRED TO INFORM FBPE. |
| | |
| | 6. ENGINEER IS TO REVIEW THE SOILS REPORT. SHEET S001 |
| | FOUNDATIONS INCLUDES A REFERENCE TO THE SOILS REPORT |
| | DATED APRIL 11, 2016. THIS REPORT WAS UPDATED ON |
| | 12/13/16. REVISE SHEET S001 OR PROVIDE A SHOP DRAWING |
| | REVIEW STAMP OR REVIEW LETTER. |
| | |
| | 7. SEE PREVIOUS LIST; "NOTICE AT RISK, THIS PERMIT IS |
| | FOR A FOUNDATION ONLY, PLEASE PROVIDE AN APPENDIX TO |
| | THE PERMIT APPLICATION, DESCRIPTION OF WORK, AS TO WHAT |
| | WORK IS TO BE ACCOMPLISHED UNDER THIS FOUNDATION |
| | PERMIT. THE CITY CONSIDERS A FOUNDATION PERMIT ANY WORK |
| | TO BE COMPLETED UNTIL THE BUILDING LEVEL IS EVEN WITH |
| | GRADE." |
| | |
| | PLEASE PROVIDE REQUESTED APPENDIX TO THE PERMIT |
| | APPLICATION SO THAT THE PERMIT DESCRIPTION CAN BE |
| | REVISED. |
| | |
| | PLEASE ALSO BE ADVISED THAT CONSTRUCTION UP TO GRADE |
| | LEVEL IS NOT A REQUIREMENT; IT IS A LIMITATION OF THE |
| | "FOUNDATION" PERMIT TYPE. CONSTRUCTION HIGHER THAN |
| | GRADE IS A "STRUCTURE" PERMIT TYPE. APPLICANT'S |
| | RESPONSE WAS TO INCREASE THE SCOPE UNDER THIS PERMIT TO |
| | INCLUDE ALL ADDITIONAL ITEMS UP TO GRADE LEVEL. THIS IS |
| | ACCEPTABLE BUT NOT REQUIRED. |
| | |
| | 8. I WAS UNABLE TO LOCATE A CODE SUMMARY FROM THE |
| | ARCHITECT WHICH INCLUDES BASIC INFORMATION SUCH AS |
| | GOVERNING CODE, OCCUPANCY CLASSIFICATIONS, BUILDING |
| | TYPE. THIS INFORMATION IS TYPICALLY INCLUDED IN THE |
| | LIFE SAFETY PLANS, BUT THOSE SHEETS WERE REMOVED FROM |
| | THE PLAN. EITHER ADVISE AS TO WHERE THIS CAN BE LOCATED |
| | OR REVISE PLAN TO INCLUDE. |
| | |
| | 9. PLEASE SEE THE SPECIFIC LANGUAGE IN FS 553.79 (7): |
| | |
| | (D) ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRESAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS CHAPTER AND CHAPTER 633. |
| | |
| | LANGUAGE ON THE ENGINEER'S PLAN IS NOT CONSISTENT WITH |
| | THE STATUTE. EITHER REVISE OR SEND RATIONALE VIA EMAIL |
| | AND I'LL FORWARD TO THE BUILDING OFFICIAL AND / OR FBPE |
| | FOR DETERMINATION AS TO WHETHER THE EXACT LANGUAGE |
| | SPECIFIED BY THE FLORIDA STATUTE IS REQUIRED. |
| | |
| | 10. ALL LIFE SAFETY PLANS WERE REMOVED. PLEASE PROVIDE |
| | A LIFE SAFETY PLAN FOR THE POOL DECK AREAS. SEE FBC B |
| | TABLE 1004.1.2, 15 SF PER PERSON IS REQUIRED FOR POOL |
| | DECKS. THE LIFE SAFETY PLAN SHOULD INCLUDE OCCUPANT |
| | LOAD, EXITS, EXIT WIDTHS FOR THIS AREA (NOT NECESSARILY |
| | FOR THE ENTIRE FLOOR, ALTHOUGH INFORMATION REGARDING |
| | ADDITIONAL OCCUPANTS IS REQUIRED IF EXITS ARE REQUIRED |
| | TO BE UTILIZED BY OTHER OCCUPANTS ON THE FLOOR). THIS |
| | IS BEING REQUESTED DUE TO ISSUES ON MORE THAN ONE |
| | PROJECT RELATED TO THIS ISSUE, AND IN SOME INSTANCES AN |
| | ADDITIONAL EXIT WAS REQUIRED. AN EMAIL WAS SENT TO THE |
| | APPLICANT REQUESTING THIS INFORMATION VIA EMAIL IF |
| | AVAILABLE. |
| | |
| | NOTE THAT A COMPREHENSIVE LIFE SAFETY REVIEW IS NOT |
| | PERFORMED ON A FOUNDATION PERMIT, BUT FOUNDATION PERMIT |
| | SHOULD INCLUDE STRUCTURAL ITEMS WHICH WOULD BE |
| | DIFFICULT TO INSTALL RETROACTIVELY. |
| | |
| | 11. SHEET E.002, THE PRINTED NAME AND LICENSE NUMBER OF |
| | THE INDIVIDUAL SIGNING AND SEALING THE PLAN, THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR THE FIRM ARE |
| | REQUIRED TO BE INCLUDED IN THE TITLE BLOCK, FS471, |
| | FAC61G15-23.001. |
| | |
| | THIS PROJECT HAS PASSED ELECTRICAL REVIEW. FUTURE |
| | SUBMITTALS INCLUDE A TITLE BLOCK IN COMPLIANCE WITH |
| | FAC61G15-23, FS 471. DO NOT REVISE AT THIS TIME UNLESS |
| | A NEW SHEET IS SUBMITTED. |
| | |
| | 12. ADVISORY, PERMIT WILL BE ISSUED AT APPLICANT'S RISK |
| | (FOUNDATION ONLY). |
| | |