Plan Review Notes
Plan Review Notes For Permit 16060825
Permit Number 16060825
Review Stop P
Sequence Number 1
Notes
Date Text
2016-07-27 13:50:371) THE SUBMITTED PLANS DO NOT REFLECT ANY INSTALLATION
 OF AN UNDERGROUND/UNDER SLAB PLUMBING SYSTEM EXCEPT ON
 THE CIVIL DRAWINGS. IS THIS FOUNDATION PERMIT ONLY FOR
 PILES / PILECAPS? PLEASE CLARIFY THE SCOPE OF WORK.WPB
 AMEND. TO FBC SEC. 107.2.1.IF ANY PLUMBING WORK IS TO
 BE DONE SUBMIT PLUMBING PLANS THAT REFLECT THE ENTIRE
 SCOPE OF PLUMBING WORK TO BE DONE
 2) CLARIFY ON THE CIVIL DRAWINGS THE PLUMBING WORK ( IF
 ANY) TO BE DONE UNDER THIS PERRMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
 .
  
  
  
  